2019-08-12 13:10:34 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NO REVISIONS ARE INDICATED ON PLAN SHEET. THE ONLY |
| CHANGE I CAN SEE IS THAT THE METER CAN IS SHOWN INSIDE |
| THE HALLWAY, WHICH IS OBVIOUSLY NOT CORRECT. PROVIDE |
| NARRATIVE OF CHANGES AND CLOUD CHANGES ON PLAN. CORRECT |
| THE LOCATION OF METER CAN ON PLAN. WPB FBC 107.2.1 |
| 2. AS A PROVISO ON THE ORIGINAL PLAN, IT WAS NOTED THAT |
| THE OUTSIDE DISCONNECT MUST BE RATED FOR THE AVAILABLE |
| FAULT CURRENT, WHICH IN A LETTER FROM FPL WAS STATED AS |
| 21110 AIC. THE DISCONNECT ON THIS PLAN STILL SHOWS A |
| RATING OF 10,000 AIC. PROVIDE CORRECTION. NEC 110.9, |
| 110.10; FBC RE E3606.3 |
| 3. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN |
| EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE |
| CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| 4. LOAD CALCULATION STATES THIS IS A 125 AMP SERVICE. |
| RISER DIAGRAM INDICATES THIS IS A 100 AMP SERVICE. |
| CORRECT DISCREPANCY. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |