2020-09-08 17:42:10VERIZON POLE BOYNTON BEACH POLYGON EMBASSY WPB2
  
 FAILED
  
 1) SURVEY
  
 A. THE SURVEY PROVIDES THE DIMENSION LINE FROM THE EDGE
 OF THE RIGHT-OF-WAY TO THE CENTER OF THE POLE AS 0.5
 FEET. THE TOP OF THE POLE FOUNDATION IS SHOWN WITH A
 2.5 FOOT ABOVE GRADE DIAMETER, WHICH MEANS THAT THE
 CENTER OF THE POLE NEEDS TO BE A MINIMUM OF 1.25 FEET
 FROM THE EDGE OF THE RIGHT-OF-WAY LINE TO NOT BE
 LOCATED ON PRIVATE PROPERTY.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THE
 CORRECTED SURVEY INFORMATION.
  
 NOTE:
  
 THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811
 TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL
 DEPTHS PRIOR TO CONSTRUCTION.
  
 THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A
 CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE
 WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES
 THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS,
 OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446