2020-07-01 16:57:34INSUFFICIENT
  
 PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE
 DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401
 OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE
 COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION.
 THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO
 REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF
 HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS,
 THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION,
 NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE
 APPROVED.
  
 1) UPDATED COMMENT: SURVEY OF UNDERGROUND FACILITIES -
 THE BASE OF THE POLE IS BEING INSTALLED UNDERGROUND SO
 THIS IS REQUIRED.
  
 A. THE SURVEY THAT WAS PROVIDED WITH THE APPLICATION
 DOES NOT SHOW THE LOCATION OF THE UNDERGROUND UTILITY
 FACILITIES THAT ARE INCLUDED ON THE ENGINEERING PLANS
 (IT SPECIFICALLY STATES THAT UNDERGROUND UTILITIES AND
 IMPROVEMENTS WERE NOT LOCATED IN NOTE #3). THE PROPOSED
 POLE HAS A 10 FOOT DEEP UNDERGROUND BURIAL. THE
 INFORMATION HAS NOT BEEN PROVIDED THAT THIS WILL NOT
 IMPACT EXISTING UTILITIES (ALL OF WHICH ARE SHOWN LESS
 THAN 10 FEET IN DEPTH). THE CROSS SECTION PLANS NEED TO
 SHOW THE POLE FOUNDATION. POT HOLES ARE REQUIRED IF
 PROPOSED POLE IS WITHIN TEN FEET OF EXISTING WATER,
 SEWER OR STORM WATER FACILITIES.
  
 B. THE ENGINEERING PLAN MUST BE BASED OFF OF THIS
 SURVEY INFORMATION.
  
 2) PUBLIC UTILITY LETTERS, TELEPHONE, NATURAL GAS,
 ELECTRIC SERVICE, AND TELEVISION CABLE - PUBLIC UTILITY
 LETTERS NEED TO BE PROVIDED BY ANY PROVIDER WITHIN FIVE
 (5) FEET OF THE PROPOSED POLE (AND THE BORE AND BORE
 PITS IF INCLUDED ON THIS APPLICATION). PLEASE NOTE THAT
 AS STATED PREVIOUSLY, THE UNDERGROUND INFORMATION WAS
 NOT PROVIDED ON THE SURVEY. THE ENGINEERING PLAN STATES
 THAT THE CONTRACTOR IS TO FIELD VERIFY UNDERGROUND
 UTILITIES; HOWEVER, THE CITY CODE REQUIRES THAT THIS BE
 PROVIDED PRIOR TO THE CITY APPROVAL. IF THERE ARE NO
 UNDERGROUND UTILITIES IN THE AREA, THIS NEEDS TO BE
 CLEARLY STATED ON THE PLANS AND HOW THIS INFORMATION
 WAS DETERMINED. HOWEVER, THE ENGINEERING PLAN SHOWS A
 GAS LINE IN THE VICINITY OF THE UNDERGROUND BORE AND
 BORE PITS.
  
 3) THE OVERALL HEIGHT OF THE POLE AND ANTENNA IS SHOWN
 AS 32 FEET ON SHEET C3 ELEVATION & EQUIPMENT PLAN AND
 38 FEET 1 INCH ON SHEET S1 ASSEMBLY ELEVATIONS. BOTH
 PLANS NEED TO SHOW THE SAME, ACCURATE HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  