Plan Review Notes For Permit 19070649 |
Permit Number |
19070649 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-18 06:36:24 | 7/18/19 1ST REVIEW DENIED A. BELISLE | | | | 1) THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON | | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED | | CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING | | PERMIT VALUATIONS. | | | | 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS | | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC | | SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED | | COMBUSTION AIR AND VENTILATION AIR SYSTEM. | | | | 3) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND | | THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF | | ANY GAS. WHAT OTHER APPLIANCES/EQUIPMENT IS SUPPLIED BY | | THIS "EXISTING GAS"? SINCE THERE IS NO RECORD OF A | | PERMIT FOR THE GAS, THE GAS MUST BE INCLUDED IN THIS | | PERMIT FOR THIS SCOPE OF WORK. WPB AMENDMENTS TO THE | | FBC SEC. 105.1. | | | | 4) PLEASE CLARIFY THE NEW 1/2" WATER LINE GOING TO THE | | WASHING MACHINE, IS THIS THE OLD LOCATION OF THE WATER | | HEATER? | | | | 5) HOW MANY GALLONS IS THE REPLACEMENT WATER HEATER ? | | | | 6) NO VALUE OR WORK DESCRIPTION WAS LISTED FOR PERMIT | | #19070651. PLEASE STATE THE WORK DECRIPTION AND VALUE | | ON THE APPLICATION | | | | ATELYO BELISLE | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6695 | | |
|