Plan Review Notes
Plan Review Notes For Permit 19070649
Permit Number 19070649
Review Stop G
Sequence Number 1
Notes
Date Text
2019-07-18 16:21:407/18/19 1ST REVIEW DENIED A. BELISLE
  
 1) THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING
 PERMIT VALUATIONS.
  
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC
 SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 3) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 ANY GAS. WHAT OTHER APPLIANCES/EQUIPMENT IS SUPPLIED BY
 THIS "EXISTING GAS"? SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE GAS, THE GAS MUST BE INCLUDED IN THIS
 PERMIT FOR THIS SCOPE OF WORK. WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
 4) PLEASE CLARIFY THE NEW 1/2" WATER LINE GOING TO THE
 WASHING MACHINE, IS THIS THE OLD LOCATION OF THE WATER
 HEATER?
  
 5) HOW MANY GALLONS IS THE REPLACEMENT WATER HEATER ?
  
 6) NO VALUE OR WORK DESCRIPTION WAS LISTED FOR PERMIT
 #19070651. PLEASE STATE THE WORK DECRIPTION AND VALUE
 ON THE APPLICATION
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  