Plan Review Notes
Plan Review Notes For Permit 19070625
Permit Number 19070625
Review Stop M
Sequence Number 1
Notes
Date Text
2019-09-23 17:09:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070625
 9/23/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: PLEASE IDENTIFY ALL NEW ROOMS ON THE
 PLAN- SECTION 107.2.1 WPB.
  
 2) M1.1: : REFER TO SECTION 809.2 FBC-EX AND PROVIDE
 MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR.
  
 3) M1.1: THERE IS A MISSING FIRE DAMPER WHERE THE 18/10
 DUCT IS PENETRATING THE FIRE-RATED WALL ABOVE DOOR 01-
 SECTION 607.5.2 FBC M
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  