Plan Review Notes
Plan Review Notes For Permit 19070551
Permit Number 19070551
Review Stop P
Sequence Number 2
Notes
Date Text
2019-09-26 09:18:11PLUMBING COMMENTS: APPROVED W/PROVISO
 1. PLUMBING PROVISO: PER WPB FBC 107.2.1 AND WPB FBC
 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL, AS AN
 ADDENDUM TO A4.21, AN 8-1/2 INCH X 11 INCH SKETCH OF
 DETAIL 3/A4.21 NOTING IN ADDITION TO THE CLEAR FLOOR
 SPACE, THE REQUIRED TURNING SPACE TO COMPLY WITH FBC
 ACC 304. THE DOCUMENTS SHALL BE SUBMITTED AS A
 SUPPORTING DOCUMENT WITH REQUIRED ARCHITECTS DIGITAL
 SIGNATURE, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. SEE RED LINED COMMENTS ON PLAN SHEETS A4.21
 AND TP4. PROCEED AT YOUR OWN RISK.
 2. VALVING ARRANGEMENT AT SINK SHALL COMPLY WITH THE
 MINIMUM REQUIREMENTS OF FBC PL 606.1. SEE REDLINED
 COMMENTS ON PLAN SHEET TP4.
  