Plan Review Notes
Plan Review Notes For Permit 19070551
Permit Number 19070551
Review Stop E
Sequence Number 2
Notes
Date Text
2019-09-26 12:34:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVISO!
  
 SPACE AVOCE THE METER AND DISCONNECT IN THE ELECTRICAL
 ROOM IS DEDICATED SPACE. F/A PANEL CANNOT BE INSTALLED
 IN THE LOCATION SHOWN ON DRAWINGS.
 110.26(E)(1)(A)