2019-09-05 17:16:36PLUMBING 1ST REVIEW**DENIED**
 1-PLUMBING SUB PERMIT APPLICATION REQUIRED. FBC 107.1
 2-SHT. A0.04 LIST 1 OF THE TOILET DISPENSER DETAILS
 SHOWING THE MEASUREMENT (7?-9?) TO THE FRONT EDGE AND
 NOT THE CENTER. FBC-ACC 604.7
 3-SHT. A0.12 NOTE #18 UNDER ACCESSIBILITY CALLS FOR THE
 TOILET DISPENSER MOUNTING AS 12? FROM THE LIP OF TOILET
 AND NOT 7?-9? AS REQUIRED IN FBC-ACC 604.7
 4-SHT. A0.12 NOTE #21 UNDER ACCESSIBILITY CALLS FOR THE
 GRAB BAR MOUNTING ABOVE THE FLOOR AND NOT TO THE TOP OF
 THE GRIPPING SURFACE. FBC-ACC 606.5
 5-SHT. A0.12 NOTE #25 CALLS TO INSULATE THE HOT WATER
 LINE AND DRAIN LINE. THE COLD LINE IS ALSO REQUIRED.
 FBC-ACC 606.5
 6-TANKLESS WATER HEATER MUST BE CAPABLE OF PRODUCING A
 HEAT RISE TO PRODUCE HOT WATER (MIN 110F) WITH 2.2 GPM
 AND NOT THE .5GPM AS CALLED OUT. THIS WATER HEATER IS
 DESIGNED FOR BATHROOM LAVATORIES WHERE .5 GPM IS
 ACCEPTABLE. PLEASE PROVIDE A WATER HEATER THAT MEETS
 FBC-PLB 604.3, 607.1
 7-PROVIDE SHUT OFF VALVES AT THE COLD WATER DOWN FEED
 AND THE HOT WATER HEATER INLET. FBC-PLB 606.1
 8) SHOW ON PLAN THE CLEAR FLOOR SPACE IN FRONT OF THE
 SINK. FBC-ACC 606
 9) ADD HAMMER ARRESTORS OR PROVIDE NOTE THAT HAMMER
 ARRESTORS ARE TO BE USED ON ALL QUICK CLOSING VALVES.
 FBC-PLB 604.9
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH ( CGA SOLUTIONS)
 [email protected]
 561-248-2703
  