Plan Review Notes
Plan Review Notes For Permit 19070530
Permit Number 19070530
Review Stop E
Sequence Number 2
Notes
Date Text
2019-09-23 11:19:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MODULAR DESIGN PLANS PROVIDED STATE THAT THERE ARE 2
 ELECTRICAL PANELS. THE LOAD CALCULATION SHOWN ON THESE
 PLANS IS 97 AMPS FOR PANEL A, AND 65 AMPS FOR PANEL B.
 THE LOAD CALCULATION PROVIDED ON THE RISER DIAGRAM DOES
 NOT MATCH THIS. PROVIDE CLARIFICATIONS AND CORRECTIONS.
 NEC 220.
 2. BASED ON LOAD CALCULATIONS, THE PROPOSED 100 AMP
 SERVICE IS NOT ADEQUATE TO SUPPLY THE LOAD. PROVIDE
 CORRECTION. NEC 215.2, 220
 3. A MAIN BREAKER IS REQUIRED AT THE SERVICE LOCATION.
 RISER PROVIDED SHOWS A 100 AMP METER CAN FEEDING #6
 WIRES WITH NO OVER CURRENT PROTECTION. THIS WIRE IS NOT
 RATED FOR 100 AMPS. THE SERVICE DOES NOT SHOW THE
 REQUIRED MAIN BREAKER. PROVIDE CORRECTION. NEC 230.70,
 310.15(B)(16)
 4. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  