Plan Review Notes
Plan Review Notes For Permit 19070414
Permit Number 19070414
Review Stop M
Sequence Number 1
Notes
Date Text
2019-08-06 13:01:37MECHANICAL PLAN REVIEW FAIL
  
 1 - PLEASE SHOW OUTDOOR AIR FLOW RATES 2017 FLORIDA
 BUILDING CODE - MECHANICAL, SIXTH EDITION TABLE
 403.3.1.1
  
 2 - NOTE AIR INTAKE OPENINGS SHALL COMPLY WITH 2017
 FLORIDA BUILDING CODE - MECHANICAL, SIXTH EDITION 401.4
 INTAKE OPENING LOCATION.
  