2019-07-13 03:39:22 | 7/13/19 DENIED | | | | THE PLANS INDICATE AN EXISTING GAS METER. THE BTU LOAD | | OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL | | BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS | | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST | | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A | | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF | | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE | | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN | | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO | | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE | | EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4, | | 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES. | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE | | APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED | | CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING | | PERMITS VALUATIONS. | | | | ATELYO BELISLE | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6695 | | | | | | | | |
|