2019-07-13 03:39:227/13/19 DENIED
  
 THE PLANS INDICATE AN EXISTING GAS METER. THE BTU LOAD
 OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES 2017 FBC FUEL GAS SECS. 401.4,
 401.8, 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS RES.
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING
 PERMITS VALUATIONS.
  