Plan Review Notes
Plan Review Notes For Permit 19070350
Permit Number 19070350
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-17 14:37:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET S 1 - THERE IS AN INDICATION OF 14' HEIGHT FOR
 FIRE APPARATUS PARKING; HOWEVER THERE ANGLE BRACES
 INDICATED ON BOTH SIDES THAT APPEAR TO ENCROACH ON THE
 14' AND NOT PROVIDE THE 13'6" MINIMUM HEIGHT
 REQUIREMENT.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY THAT IT MEETS
 MINIMUM MHEIGHT REQUIRMENTS.
  
  
 2) THERE DOES NO APPEAR TO BE ANY LIGHTING. THE
 FPROPOSED DOES NOT MEET THE MINIMUM CANDELA LIGHTING
 REQUIRED.
  
 WILL LIGHTING BE PROVIDED?
  
 PLEASE PROVIDE DETAILS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  