2019-09-23 11:04:33 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19070244 |
| 9/23/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THE MECHANICAL PLANS WERE APPROVED ON 8/14/19 WITH THE |
| PROVISOS LISED BELOW. THE REVISED PLAN SUBMITTED ON |
| 9/6/19 TO ADDRESS THOSE PROVISOS IS NOT IN COMPLIANCE. |
| SEE PROVISOS LISTED BELOW |
| |
| |
| MECHANICAL PROVISOS: |
| |
| THE MECHANICAL PLAN IS APPROVED WITH EXCEPTION- A |
| REVISION IS REQUIRED TO ADDRESS THESE ISSUES: |
| |
| 1) PROVIDE AN INDEPENDENT EXHAUST VENTILATION SYSTEM |
| FOR THE LAB IF CHEMICAL PROCESSING OR TESTING IS |
| PERFORMED IN THE ROOM. |
| |
| 2) THE POLISH ROOM AND TOILET ROOM EXHAUST DUCTS MUST |
| BE RUN INDEPENDENTLY FROM INLET TO OUTLET. |
| |
| 3) THE TRANSFER DUCT (JUMPER) RETURNING AND |
| RECIRCULATING AIR FROM THE LAB TO THE CORRIDOR IS NOT |
| ALLOWED. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |