Plan Review Notes
Plan Review Notes For Permit 19070244
Permit Number 19070244
Review Stop MEDGAS
Sequence Number 2
Notes
Date Text
2020-03-06 16:41:3703/05/20 2ND MEDICAL GAS REVISION REVIEW **DENIED**
 WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
 REFERENCE: NFPA 99 2012 EDITION
  
 1. EQUIPMENT SPECIFICATIONS DO PROVIDE GENERIC DETAILS
 FOR CONNECTIONS, BUT DO NOT ADDRESS THE DISTRIBUTION
 AND CONFIGURATIONS OF THIS EQUIPMENT LAY OUT THAT IS
 NEEDED TO GUIDE THE CONTRACTOR AND INSTALLERS AS WELL
 AS ALLOWING THE INSPECTOR TO INSPECT FOR NFPA 99
 COMPLIANCE AND TO CONFIRM THAT THE INSTALLATION
 CONFORMS TO THE DESIGNER?S INTENT, PROVIDE DETAILS ON
 THE PLAN THAT CLEARLY INDICATE THE MANIFOLDS AND PIPING
 DISTRIBUTION AND CONFIGURATIONS REQUIRED FOR A COMPLETE
 INSTALLATION. THIS INCLUDES A RISER DIAGRAMS FOR ALL
 THE MEDICAL GAS PIPING TO BE INSTALLED. PROVIDE
 ISOMETRIC DRAWING FOR MED GAS INCLUDING VACUUM EXHAUST
 PER THE WPB AMENDMENTS TO FBC 107.3.5.1.3(13).
  
 2. ALL WATER TUBES MEDICAL GAS SHALL BE IN ACCORDANCE
 WITH NFPA 99 2012 SECTION 5.3.7.2.1. WITH ASTM B 819,
 STANDARD SPECIFICATION FOR SEAMLESS COPPER.
  
 3. THERE ARE 2 P-3 SHEETS WHICH ON HAS A REVISION DATE
 SO PLEASE DELETE THE ONE NOT NEEDED PER THE WPB AMEND
 TO FBC 107.2.1.
  
 4. PLEASE PROVIDE SPECIFICATION FOR VACUUM PUMP AND FOR
 AIR COMPRESSOR SHOWING COMPLIANCE PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 5. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING THE DENTAL
 CHAIRS, TANKS AND VALVES PER THE WPB AMEND TO FBC
 107.2.1.
  
 6. THE AREA(S) HOUSING THE VACUUM PUMP AND AIR
 COMPRESSOR SHALL BE VENTILATED PER NFPA 99 SECS.
 5.1.3.3.3.3, 5.1.3.6.3.1, 5.1.3.7.1.1.
  
 7. PIPING SYSTEMS FOR CATEGORY 3 GASES SHALL NOT BE
 USED AS GROUNDING ELECTRODES PER THE NFPA 99 2012 SEC.
 5.3.13.2.2.
  
 8. ALL DOCUMENTATION PERTAINING TO INSPECTIONS AND
 TESTING SHALL BE MAINTAINED ON-SITE PER THE NFPA 99
 2012 SEC. 5.3.9.1.5.
  
 9. PROVIDE A DETAIL FOR RESTRAINTS ON THE OXYGEN TANK
 INCLUDING WALL ANCHORAGE PER THE WPB AMEND TO FBC
 107.2.1.
  
 10. A SEPARATE PERMIT IS REQUIRED FOR MED GAS PER THE
 2017 WPB A TO FBC 107.5.
  
 11. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM
 EXHAUST AND RELIEF PIPING ON THE ROOF PLAN, IT SHALL BE
 DISCHARGED ABOVE ROOF IN A SEPARATE VENT PER THE NFPA
 99 2012 SEC. 5.3.8.3.11. (1).
  
 12. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS
 SYSTEM IS DESIGNED TO BE PER THE NFPA 99 CHAPTER 4,
 CATEGORY 3.
  
 13. PROVIDE COMPLETED INSTALLATION MANUALS FOR ALL NEW
 MED GAS EQUIPMENT IN DETAIL PER THE 2017 WPB A TO
 SECTION FBC 107.3.5.
  
 14. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS PER
 THE WPB AMEND TO FBC 107.2.1.
  
 15. PLEASE PROVIDE A LEGEND FOR ALL GAS VALVES PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 16. PLEASE PROVIDE DETAIL HOW PIPING IS GOING TO BE
 SUPPORTED IN ACCORDANCE WITH NFPA 2012 5.3.7.3.3 PIPE
 SUPPORT. PIPE SUPPORT SHALL BE IN ACCORDANCE.
  
 17. FILTER MUST COMPLY WITH NSF 42 PLEASE SUBMIT
 MANUFACTURES SPECIFICATION FOR COMPLIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 18. PLEASE PROVIDE HOW WARNING SYSTEM WILL ABIDE PER
 THE 5.3.6.22.1 WARNING SYSTEMS FOR MEDICAL GAS SYSTEMS.
  
 19. PLEASE PROVIDE HOW PIPE IS GOING TO BE LABELED PER
 THE 2012 NFPA 5.3.11.1.4 (1) AT INTERVALS OF NOT MORE
 THAN 6.1 M (20 FT).
  
 20. PROVIDE PIPING DETAIL OF CONTROL VALVES AND TANK
 MANIFOLD ALSO DETAIL OF HOW TANK IS SECURED PER WPB
 AMEND TO FBC 107.2.1 AND NFPA 99.
  
 21. PLEASE SHOW WHERE EMERGENCY VALVE IS LOCATED AND
 LABELED PER THE 2012 NFPA 5.3.6.19.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved