2020-02-10 18:24:32 | 3RD REVIEW:.19070244 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| MED GAS COMMENTS: |
| |
| 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE |
| INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED. |
| INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON |
| JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031 |
| |
| 2. PROVIDE NOTE ON PLAN MED GAS SHALL COMPLY WITH NFPA |
| 99 |
| |
| 3. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION |
| GUIDE FOR THE NEW VACUUM PUMP AND AIR COMPRESSOR. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 4. SHT. P3 KEY NOTE A REFERENCES SHT P6 BUT P6 HAS NOT |
| BEEN UPLOADED PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 5. WHAT TYPE OF PIPING IS BEING USED FOR THE COMPRESSED |
| AIR LINES. PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. SHT P3 UNDER PLUMBING KEYNOTES ( DENTAL) REFERENCES |
| DENTAL DRAWINGS THEY HAVE NOT BEEN DOWNLOADED PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| END OF COMMENTS |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |