Plan Review Notes
Plan Review Notes For Permit 19070244
Permit Number 19070244
Review Stop M
Sequence Number 1
Notes
Date Text
2019-08-02 07:51:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070244
 8/1/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE RETURN AIR TRANSFERS FROM THE ROOMS
 INTO THE CORRIDORS (LABELED HALLS ON THE PLAN) ARE
 PROHIBITED PER SECTION 601.2 FBC M.
  
 2) M1: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER
 SF. IS REQUIRED FOR THE LAB AND RECIRCULATION OF AIR
 FROM THE ROOM IS PROHIBITED EXCEPT WHERE THE AIRSTREAM
 CONSISTS OF NOT MORE THAN 10% OF THE AIR SUPPLIED TO
 THE ROOM- TABLE 403.3.1.1 FOOTNOTE G.
  
 3) REFER TO SECTIONS 510.1 & 510.2 FBC M AND CLARIFY
 THE PROCESSES THAT OCCUR IN THE LAB AND WHAT MATERIALS
 ARE STORED AND USED FOR PROCESSING IN THE ROOM.
 PLEASE PROVIDE A LIST OF MATERIALS AND THEIR
 QUANTITIES- SECTION 414.1.3 FBC B.
  
 510.2 WHERE REQUIRED.
  
 A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER
 OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF
 HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST
 SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE
 POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS:
 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT
 IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER
 FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED
 ROOM TEMPERATURE.
 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 4 IS PRESENT IN ANY CONCENTRATION.
 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS
 EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION
 OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY.
  
 EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1,
 EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE
 EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A
 HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN
 CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL
 CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION
 TOXICITY.
  
 4) M1: PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES, AND AIR BALANCE CALCULATIONS- TABLE
 403.3.1.1 AND SECTION 501.4 FBC M.
  
 5) M1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 POLISH ROOM, AND INDICATE WHAT TYPE OF FUMES, MISTS, OR
 VAPORS ETC. ARE BEING EXHAUSTED FROM THE ROOM. ARE
 THEIR ANY FUME OR CAPTURE HOODS IN THE ROOM OR IN THE
 LAB?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  