2019-08-02 07:51:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19070244 |
| 8/1/2019 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M1: THE RETURN AIR TRANSFERS FROM THE ROOMS |
| INTO THE CORRIDORS (LABELED HALLS ON THE PLAN) ARE |
| PROHIBITED PER SECTION 601.2 FBC M. |
| |
| 2) M1: EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER |
| SF. IS REQUIRED FOR THE LAB AND RECIRCULATION OF AIR |
| FROM THE ROOM IS PROHIBITED EXCEPT WHERE THE AIRSTREAM |
| CONSISTS OF NOT MORE THAN 10% OF THE AIR SUPPLIED TO |
| THE ROOM- TABLE 403.3.1.1 FOOTNOTE G. |
| |
| 3) REFER TO SECTIONS 510.1 & 510.2 FBC M AND CLARIFY |
| THE PROCESSES THAT OCCUR IN THE LAB AND WHAT MATERIALS |
| ARE STORED AND USED FOR PROCESSING IN THE ROOM. |
| PLEASE PROVIDE A LIST OF MATERIALS AND THEIR |
| QUANTITIES- SECTION 414.1.3 FBC B. |
| |
| 510.2 WHERE REQUIRED. |
| |
| A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER |
| OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF |
| HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST |
| SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE |
| POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: |
| 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT |
| IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER |
| FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED |
| ROOM TEMPERATURE. |
| 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| RATING OF 4 IS PRESENT IN ANY CONCENTRATION. |
| 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS |
| EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION |
| OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. |
| |
| EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, |
| EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE |
| EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A |
| HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN |
| CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL |
| CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION |
| TOXICITY. |
| |
| 4) M1: PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES, AND AIR BALANCE CALCULATIONS- TABLE |
| 403.3.1.1 AND SECTION 501.4 FBC M. |
| |
| 5) M1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| POLISH ROOM, AND INDICATE WHAT TYPE OF FUMES, MISTS, OR |
| VAPORS ETC. ARE BEING EXHAUSTED FROM THE ROOM. ARE |
| THEIR ANY FUME OR CAPTURE HOODS IN THE ROOM OR IN THE |
| LAB? |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |