Plan Review Notes For Permit 19070209 |
Permit Number |
19070209 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-09 17:39:15 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19070209 | | 7/9/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) DUCT WORK WAS NOT INCLUDED IN THE ORIGINAL PLANS | | APPROVED UNDER PERMIT #19040945. PLEASE INDICATE THE | | INCREASE IN VALUE FOR THE PROPOSED WORK ON THE REVISION | | APPLICATION, AND LABEL THE AIR HANDLER AS EITHER NEW | | (REPLACED) OR EXISTING. | | | | 2) THE APPROVED PLANS UNDER PERMIT #19040945 SHOWS THE | | MASTER SUITE TO BE THE BEDROOM THAT HAS THE WALK-IN | | CLOSET. PLEASE NOTE THAT ALL AIR FROM A MASTER SUITE | | SHALL BE RETURNED. PLEASE INCREASE THE SIZE OF THE | | RETURN GRILL R1 IN COMPLIANCE WITH SECTION 601.6 ITEM | | 3. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | BUILDING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|