2019-07-08 06:18:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SATISFY ALL REQUIREMENTS FROM ZONING DEPT.
  
 2. PROVIDE SPEC SHEETS SHOWING UL OR OTHER NRTL LISTING
 FOR ALL LIGHTING AND LEGRAND CHARGING STATIONS. FBC
 107.2.1 NEC 90.7, 110.2, 110.3B
  
 3. PROVIDE STRUCTURAL DETAIL FOR POLE/BASE FOR POLE
 MOUNTED LIGHT, INCLUDE WIND LOADS. FBC 107.2.1 FBC 1609
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.