Plan Review Notes
Plan Review Notes For Permit 19070169
Permit Number 19070169
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-16 15:38:05BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19070169
 REVIEWED: JULY 16, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 1004.1 FBC[B]DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
  -PLEASE PROVIDE AREA, OCCUPANCY AND OCCUPANT LOAD FOR
 THE EXISTING SPACE LABELED MID FLORIDA ARMORED SPACE.
 STORAGE AREA CAN USE STORAGE OCCUPANY FOR OCCUPANT
 LOAD.
  -IF THE OCCUPACY EXCEEDS 49 THAN 2 EXITS ARE REQUIRED
 (SEE COMMENT 2)
  
 2) 1006.1 FBC[B]GENERAL. THE NUMBER OF EXITS OR EXIT
 ACCESS DOORWAYS REQUIRED WITHIN THE MEANS OF EGRESS
 SYSTEM SHALL COMPLY WITH THE PROVISIONS OF SECTION
 1006.2
  -THE LIFE SAFETY PLANS SHOWS ADDITIONAL EXIT THROUGH
 THE OTHER TENANT SPACE. IT APPEARS THAT BATHROOMS ARE
 SHARED, BUT THE OTHER SPACE THAT IS HATCHED IS OPEN AND
 WOULDN?T APPEAR TO BE A MEANS OF EGRESS.
  -IS THE BUILDING SPRINKLED?
 PLEASE ADD TO DATA TABLE SO THE MAXIMUM COMMON PATH OF
 TRAVEL CAN BE ESTABLISHED.
 ACCORDING TO A-2 BUILDING ANALYSIS COMMON PATH OF
 TRAVEL IS 75 FEET AND MAX DEAD END CORRIDOR IS 20 FEET.
 THE DRAWING SHOWS 100 FEET FROM OFFICE 6 AND DEAD
 COORIDOR IS OVER 20 FEET.
  
 NOTES:
 WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  