Plan Review Notes For Permit 19070148 |
Permit Number |
19070148 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-08 07:47:07 | 7/8/19 A. BELISLE DENIED. SHOW THE LOCATION OF ALL MP | | (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE | | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 | | FBC FUEL GAS SEC. 409.4, | | | | SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS | | APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE | | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC | | SEC.304.9.3 COMBINED COMBUSTION AIR AND VENTILATION AIR | | SYSTEM. | | | | SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE | | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR | | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS | | SYSTEM 2017 FBC FUEL GAS SEC. 402.3 | | | | | | ATELYO BELISLE | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6695 | | | | | | | | |
|