2019-07-08 07:47:077/8/19 A. BELISLE DENIED. SHOW THE LOCATION OF ALL MP
 (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017
 FBC FUEL GAS SEC. 409.4,
  
 SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC
 SEC.304.9.3 COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
  
 SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3
  
  