Plan Review Notes For Permit 19070089 |
Permit Number |
19070089 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-19 09:31:20 | 1ST REVIEW: 19070089 | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. SEE BUILDINGS COMMENTS | | | | 2. PROVIDE EXISTING OR DEMO PLAN. PER WPB AMEND TO FBC | | 107.2 | | | | 3. SHOW LEVEL OF ACCESSIBILITY IN BATHROOMS AND WATER | | FOUNTAIN INCLUDE DIMENSIONS . PER FBC ACC CH 6- 602, | | 603, 604, 606, 609 | | | | 4. SHOW ALL PLUMBING FIXTURES INCLUDE DIMENSIONS IN THE | | BATHROOMS.PER WPB AMEND TO FBC 107.2 | | | | 5. ALL FIXTURE IN KITCHEN AREA SHALL DISCHARGE THROUGH | | GREASE INTERCEPTOR. PER FBC PL 1003.3.1 | | | | 6. INDICATE UNIT NUMBER IN THE ADDRESS ON THE PLAN AND | | PERMIT APPLICATION. PER WPB AMEND TO FBC 107.2 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|