Plan Review Notes
Plan Review Notes For Permit 19070089
Permit Number 19070089
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-08 15:27:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO
 DETERMINE COMPLAINCE WITH THE FLORIDA FIRE PREVETNION
 CODE.
  
 PLEASE PROVIDE A DETAILED REVIEW OF WHAT THIS
 EDUCATIONAL OCCUPONACY IS, DIMENSION OF ALL
 ROOMS/SPACES, TOTAL SQUARE FOOTAGE.HOURS OF OPERATION,
 NUMBER OF STUDENTS, AGE OF STUDENTS, ETC.
  
  
  
  
 2) THERE IS NO INDICATION OF COMPLINACE WITH ANY FIRE
 CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101,
 INCLUDING CHAPTE 14, NEW EDUCATIONAL OCCUPANCIES
  
 PLEASE REVIEW AND ENSURE COMPLIANCE
  
  
  
 3) THERE IS NO INDICATION OF A LIFE SAFETY PLAN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND
 SPECIFICATIONS TO ENSURE COMPLIANCE WITH APPLICABLE
 CODES AND
 STANDARDS.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN
  
  
  
  
 4) THERE APPEARS TO ONE FIRE ALARM DEVICE.
  
 PER NFPA 101, CH. 14, NEW EDUCATIONAL OCCUPANCIES.
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6.
  
 PLEASE PROVIDE FOR THE APPLICABLE FIRE ALARM SYSTEM AND
 A NOTE OF INTENT TO PROVIDE THE FIRE ALARM SYSTEM PER
 THE APPLICABLE CODE.
  
 ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 5) THERE IS NO INDICATIONS OF A FIRE SPRINKLER SYSTEM.
  
 PER NFPA 101, CH. 14, NEW EDUCATIONAL OCCUPANCIES.
  
 14.3.5 EXTINGUISHMENT REQUIREMENTS.
 14.3.5.1* EDUCATIONAL OCCUPANCY BUILDINGS EXCEEDING
 12,000 FT2
 (1120 M2) SHALL BE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION
 9.7.
  
 PLEASE PROVIDE APPLICABLE INFORMATION TO DETERMINE IF A
 FIRE SPRINKLER SYSTEM IS REQUIRED.
  
  
  
 6) THERE ARE NO INDICATIONS OF DOOR HARDWARE.
  
 PLEASE REVIEW NFPA 101 CH 14 AND PROVIDE APPLICABLE
 DOOR INFORMATION, HARDWARE AND LOCKING DEVICES PER THE
 CODE.
  
 14.2.2.2 DOORS.
 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7.
  
  
  
  
 7) THERE IS AN INDICATION OF A "SPACE OWNED BY OTHERS"
 THAT HAS A DOOR TO THIS PROPOSED OCCUPANCY.
  
 WHAT IS THE PURPOSE/OCCUPANCY TYPE OF THAT SPACE?
  
 THE OCCUPANCY IS REQUIRED TO BE SEPARATED BY A FIRE
 RATING PER NFPA 101, CH 6 OCCUPANCY CLASSIFICATION.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF
 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED
 OCCUPANCY.
  
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE PROVIDE DETAILS AND THE REQUIRED SEPARATION.
  
  
  
  
 8) THERE IS NO INDICATION OF THE ROOM/SPACES FLOOR,
 WALL AND CEILING FINISHES
  
 14.3.3 INTERIOR FINISH.
 14.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 14.3.3.2* INTERIOR WALL AND CEILING FINISH. INTERIOR
 WALL AND
 CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE
 PERMITTED AS FOLLOWS:
 (1) EXITS ? CLASS A
 (2) OTHER THAN EXITS ? CLASS A OR CLASS B
 (3) LOW-HEIGHT PARTITIONS NOT EXCEEDING 60 IN. (1525
 MM) AND
 USED IN LOCATIONS OTHER THAN EXITS ? CLASS A, CLASS B,
 OR
 CLASS C
 14.3.3.3 INTERIOR FLOOR FINISH.
 14.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 14.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS
 CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS
 COMPLYING
 WITH 14.3.6 SHALL BE NOT LESS THAN CLASS II.
 14.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE.
  
 PLEASE PROIVDE DETAILS INDICATING COMPLIANCE
  
  
  
  
 9) THERE ARE EXIT SIGNS INDICATED BY THEY DO NOT
 INDICATE TYPE.
  
 PER NFPA 101, CH 14
  
 14.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
 14.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9.
 14.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PLEASE PROVIDE DETAILS INDICATING COMPLIANCE WITH THE
 ABOVE.
  
  
 11) THERE IS STORAGE INDICATED IN A CENTER/MAIN AREA.
  
 EXITS CAN NOT PASS THROUGH A HIGHER HAZARD AREA.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 12) THERE DOES NOT APPEAR TO BE CODE COMPLIANT EXITS.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 14.2.4 NUMBER OF MEANS OF EGRESS.
 14.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4.
 14.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN
 ACCORDANCE
 WITH THE FOLLOWING CRITERIA:
 (1) THEY SHALL BE PROVIDED ON EVERY STORY.
 (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY
 STORY AND
 MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL BE
 PERMITTED TO
 BE COMMON FOR THE DISTANCE PERMITTED AS COMMON PATH OF
 TRAVEL BY 14.2.5.3.
 14.2.5 ARRANGEMENT OF MEANS OF EGRESS. SEE ALSO SECTION
 7.5.
 14.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
 14.2.5.4 EVERY ROOM OR SPACE LARGER THAN 1000 FT2 (93
 M2) OR WITH
 AN OCCUPANT LOAD OF MORE THAN 50 PERSONS SHALL COMPLY
 WITH THE
 FOLLOWING:
 (1) THE ROOM OR SPACE SHALL HAVE A MINIMUM OF TWO EXIT
 ACCESS
 DOORS.
 (2) THE DOORS REQUIRED BY 14.2.5.4(1) SHALL PROVIDE
 ACCESS TO
 SEPARATE EXITS.
 (3) THE DOORS REQUIRED BY 14.2.5.4(1) SHALL BE
 PERMITTED TO OPEN
 ONTO A COMMON CORRIDOR, PROVIDED THAT SUCH CORRIDOR
 LEADS TO
 SEPARATE EXITS LOCATED IN OPPOSITE DIRECTIONS.
  
  
  
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL