2020-02-04 07:28:29 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19070081 |
| ADD: 5601 GREENWOOD AVE. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ?????????????????? |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 3RD REVIEW |
| DATE: TUES. FEB. 04/ 2020 |
| ACTION: PASSED |
| |
| 1) NOTICE ONLY. WALK-IN COOLERS REQUIRE THEIR OWN |
| PERMIT, REVIEW AND ASSOCIATED FEES. |
| |
| 2) NOTICE ONLY. TRUSS LAYOUT AND ENGINEERING SHEETS ARE |
| TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD, |
| SHOP DRAWING STAMP OF APPROVAL AFFIXED BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. |
| |
| 3) ROOFING PROVISO: FROM THE DESIGNER OF RECORD: |
| SUB-SYSTEM NO. 32 IS WHAT WE ARE USING IN THE NEMO |
| REPORT. THE SYSTEM IS AS FOLLOWS: SLOPED PLYWOOD |
| DECK-MECHANICALLY ATTACHED DENSDECK PRIME 4X8 SHEETS |
| USING #12 SCREWS /3" INSULATION PLATES USING 18 |
| FASTENERS PER BOARD IN THE FIELD, 27 IN THE PERIMETER |
| AND 36 IN THE CORNERS. ADHERE TPO SET IN SOLVENT BASED |
| BONDING ADHESIVE. ONCE A GENERAL CONTRACTOR IS |
| SELECTED, THE GC WILL ENGAGE THE ROOFING SUB-CONTRACTOR |
| TO PRODUCE SIGNED AND SEALED SHOP DRAWINGS, INCLUDING |
| CALCULATIONS. THE STRUCTURAL ENGINEER WILL REVIEW AND |
| WILL AFFIX THEIR SHOP DRAWING STAMP BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. |