2019-12-10 13:58:59 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19070081 |
| ADD: 5601 GREENWOOD AVE. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ?????????????????? |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2ND REVIEW |
| DATE: TUES. DEC. 10/ 2019 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. SEMI- COMPLIED. SHEET 004-A020 LIFE |
| SAFETY PLAN UNDER THE HEADING BUILDING DATA THERE IS A |
| DISCREPANCY IN WHAT AREA IS CONDITIONED SPACE AND TOTAL |
| SQ. FT. AREA BETWEEN THE FLOOR PLAN AND THE ENERGY |
| CALCULATIONS PROJECT SUMMARY. THE FLOOR PLAN INDICATES |
| 4,202 SF WHILE THEY PROJECT SUMMARY INDICATES 4,030 SF. |
| THE FLOOR PLAN INDICATES THE TOTAL SQUARE FEET UNDER |
| ROOF AS 7,150 SF WHILE THE ENERGY CALC. PROJECT SUMMARY |
| INDICATES 6582 SF. DISCREPANCY IN THE FOOTAGE BETWEEN |
| THE DOCUMENTS SUBMITTED. |
| |
| 2) SHEET 008-A-100: |
| |
| 2A) SEMI-COMPLIED. THERE ARE DISCREPANCIES IN THE |
| REFERENCE FLOOR PLAN AND THE DIMENSION PLAN. THERE |
| SEEMS TO BE A DISCREPANCY BETWEEN THE HOURLY RATING ON |
| THE WALL BETWEEN THE CREMATORY AND VIEWING ROOM. THE |
| WALL IDENTIFICATION TAG INDICATES WALL TYPE P6. THE |
| FLOOR PLAN INDICATES A 90 MINUTE RATED ROLL |
| DOWN FIRE SHUTTER (FBC-B TABLE 716.5) WITH FUSIBLE |
| LINK. A 90 MINUTE OPENING PROTECTIVE WOULD BE FOR A 2 |
| HOUR FIRE RATED WALL. IT WOULD APPEAR THERE IS A TYPO |
| ON WALL TYPE P6 AS A 21 HOUR FIRE RATED WALL. WALL |
| SHOULD BE DESIGNED FOR 100 % DESIGN LOAD AND FIRE FROM |
| EITHER SIDE. |
| |
| 2B) SEMI-COMPLIED CORRECTING THE TYPO SHOULD RESULT IN |
| COMPLIANCE. THE SAME HOLD TRUE FOR THE WALLS SEPARATING |
| THE CREMATORY/ RECEIVING # 1 AND THE PROCESSING ROOM/ |
| ELECTRIC ROOM. THESE WALLS ARE IDENTIFIED WITH A WALL |
| TAG P6 (1 HOUR FIRE RATING) WHEREAS THE DOOR 120 IS |
| INDICATED IN THE DOOR SCHEDULE REQUIRING A 90 MINUTE |
| OPENING PROTECTIVE (FBC-B TABLE 716.5). DISCREPANCY |
| BETWEEN WALL AND OPENING PROTECTIVE RATINGS. |
| |
| 2C)(1-2) COMPLIED. |
| |
| 3) COMPLIED |
| |
| 4) INFORMATIONAL ONLY NO REPLY REQUIRED. WALK-IN |
| COOLERS REQUIRE THEIR OWN PERMIT, REVIEW AND ASSOCIATED |
| FEES. |
| |
| 5-7) COMPLIED. |
| |
| 8) NOTICE ONLY. TRUSS LAYOUT AND ENGINEERING SHEETS ARE |
| TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD, |
| SHOP DRAWING STAMP OF APPROVAL AFFIXED BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. |
| |
| 9) COMPLIED. |
| |
| 10) SEMI-COMPLIED. SUBMITTED A PRODUCT APPROVAL REPORT |
| BUT THERE WERE TECHNICAL SHEETS INCLUDED. PLEASE SHOW |
| COMPLIANCE WITH: PLEASE IDENTIFY THE FOLLOWING |
| REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE |
| ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN |
| ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, |
| CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS |
| AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND |
| THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE |
| REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE |
| SUBMISSION TO THE BUILDING DEPARTMENT. |
| 1ST ROUND OF COMMENTS. SHEET M201 NOTE # 7 MECHANICAL |
| CONTRACTOR TO SUPPLY ROOF TOP STANDS FOR COOL CELL |
| CONDENSER. THE ROOF TOP A/C STAND PRODUCT APPROVAL WILL |
| NEED TO BE SUBMITTED, REVIEWED BY THE DESIGNER OF |
| RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS |
| CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP |
| COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF |
| HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED |
| THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT |
| VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND |
| TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY |
| THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO |
| THE BUILDING DEPARTMENT. |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 11-14) COMPLIED. |
| |
| 15) ROOFING PROVISO: FROM THE DESIGNER OF RECORD: |
| SUB-SYSTEM NO. 32 IS WHAT WE AARE USING IN THE NEMO |
| REPORT. THE SYSTEM IS AS FOLLOWS: SLOPED PLYWOOD |
| DECK-MECHANICALLY ATTACHED DENSDECK PRIME 4X8 SHEETS |
| USING #12 SCREWS /3" INSULATION PLATES USING 18 |
| FASTENERS PER BOARD IN THE FIELD, 27 IN THE PERIMTER |
| AND 36 IN THE CORNERS. ADHERE TPO SET IN SOLVENT BASED |
| BONDING ADHESIVE. ONCE A GENERAL CONTRACTOR IS |
| SELECTED, THE GC WILL ENGAGE THE ROOFING SUB-CONTRACTOR |
| TO PRODUCE SIGNED AND SEALED SHOP DRAWINGS, INCLUDING |
| CALCULATIONS. THE STRUCTURAL ENGINEER WILL REVIEW AND |
| WILL AFFIX THEIR SHOP DRAWING STAMP BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. |
| |
| 16) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| |
| 17) DIGITAL REVIEWS. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |