Plan Review Notes
Plan Review Notes For Permit 19070081
Permit Number 19070081
Review Stop R
Sequence Number 1
Notes
Date Text
2019-08-19 15:35:33ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 THE SUBMITTED REPORT NEMO REPORT HAS OVER 100 PAGES OF
 SUB-SYSTEMS AND ASSOCIATED PRESSURES, SOME CAN HAVE
 ENHANCED FASTENING AND SOME CANNOT. PLEASE IDENTIFY
 WHICH SUB-SYSTEM IS TO BE INSTALLED.
  
  