2019-08-23 14:54:22 | 1ST REVIEW: 19070081 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1.SHOW HEIGHT OF BREAKROOM SINK SHALL BE MAX 34"SHT |
| A400 DETAIL #8. PER FBC ACC 606.2-3 |
| |
| 2. SHT. A401 ADDRESS THE FOLLOWING COMMENTS. PER WPB |
| AMEND TO FBC 107.2.1 |
| A)GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4 |
| B)TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| DISPENSER. PER FBC ACC 604.7 |
| C) PROVIDE DIMENSIONS ON THE CLEAR FLOOR SPACE ON THE |
| TOILET AND LAVATORY. FBC ACC 604.3.1 ,606.2 |
| D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| MINIMUM ON THE OTHER SIDE.FBC ACC 604.5.2 |
| E) THE HIGH SPOUT ON THE WATER FOUNTAIN SHALL BE 38 MIN |
| FBC ACC 602.7 |
| |
| 3.SHT. P003 P101 THE FLOOR DRAIN UNDER THE OUTSIDE PREP |
| TABLE IS NOT VENTED IT SHALL BE VENTED BEFORE IT |
| CONNECTS TO THE BUILDING DRAIN. PER FBC PL 1002.4 |
| |
| 5. HOW DOES THE PUBLIC HAVE ACCESS TO THE WATER |
| FOUNTAIN IT APPEARS THEY WOULD HAVE TO TRAVEL THROUGH A |
| WORK AREA. PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE |
| FOLLOWING. |
| A) BOOSTER PUMP. |
| B) ASPIRATOR. |
| C) ALL BACKFLOW DEVICES THEY SHALL BE LEAD FREE. |
| |
| 7. SHOW ACCESSIBILITY FOR THE SHOWER PER FBC ACC |
| 608.2.1 / 608.3.1 / 608.4 / 608.5.1 / 608.6 / 609.4 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |