Plan Review Notes
Plan Review Notes For Permit 19070081
Permit Number 19070081
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-23 14:54:221ST REVIEW: 19070081
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.SHOW HEIGHT OF BREAKROOM SINK SHALL BE MAX 34"SHT
 A400 DETAIL #8. PER FBC ACC 606.2-3
  
 2. SHT. A401 ADDRESS THE FOLLOWING COMMENTS. PER WPB
 AMEND TO FBC 107.2.1
 A)GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
 B)TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
 C) PROVIDE DIMENSIONS ON THE CLEAR FLOOR SPACE ON THE
 TOILET AND LAVATORY. FBC ACC 604.3.1 ,606.2
 D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE.FBC ACC 604.5.2
 E) THE HIGH SPOUT ON THE WATER FOUNTAIN SHALL BE 38 MIN
 FBC ACC 602.7
  
 3.SHT. P003 P101 THE FLOOR DRAIN UNDER THE OUTSIDE PREP
 TABLE IS NOT VENTED IT SHALL BE VENTED BEFORE IT
 CONNECTS TO THE BUILDING DRAIN. PER FBC PL 1002.4
  
 5. HOW DOES THE PUBLIC HAVE ACCESS TO THE WATER
 FOUNTAIN IT APPEARS THEY WOULD HAVE TO TRAVEL THROUGH A
 WORK AREA. PER WPB AMEND TO FBC 107.2.1
  
 6. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 FOLLOWING.
 A) BOOSTER PUMP.
 B) ASPIRATOR.
 C) ALL BACKFLOW DEVICES THEY SHALL BE LEAD FREE.
  
 7. SHOW ACCESSIBILITY FOR THE SHOWER PER FBC ACC
 608.2.1 / 608.3.1 / 608.4 / 608.5.1 / 608.6 / 609.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]