2019-08-21 14:51:02PLAN DENIED
 1) REFER TO SECTION 306.1 FBC (M) 2017
 YOU MUST BE ABLE TO REMOVE THE EXHAUST FANS THROUGH
 THE ACCESS DOORS ON THE HARD CEILING
 2) PLEASE EXPLAIN WHAT THE BAROMETRIC RELIEF DAMPER
 IS FORE ON PAGE M 101 OF THE PLAN
 3) MISSING CEILING RADIATION DAMPERS ON 16 X 16
 DUCT ON EXHAUST FANS 3 & 4 PAGE M 101 OF THE PLAN
 607.3.3.4 FBC (M) 2017
 4) PROVIDE NOA FOR OUTSIDE LOUVERS. SECTION 107 FBC
 2017
 5) REFER TO SECTION 306.5.1 SLOPED ROOF. SERVICE
 PLATFORM AND GUARDS
 2017 FBC (M)
  