Plan Review Notes For Permit 19070081 |
Permit Number |
19070081 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-21 14:51:02 | PLAN DENIED | | 1) REFER TO SECTION 306.1 FBC (M) 2017 | | YOU MUST BE ABLE TO REMOVE THE EXHAUST FANS THROUGH | | THE ACCESS DOORS ON THE HARD CEILING | | 2) PLEASE EXPLAIN WHAT THE BAROMETRIC RELIEF DAMPER | | IS FORE ON PAGE M 101 OF THE PLAN | | 3) MISSING CEILING RADIATION DAMPERS ON 16 X 16 | | DUCT ON EXHAUST FANS 3 & 4 PAGE M 101 OF THE PLAN | | 607.3.3.4 FBC (M) 2017 | | 4) PROVIDE NOA FOR OUTSIDE LOUVERS. SECTION 107 FBC | | 2017 | | 5) REFER TO SECTION 306.5.1 SLOPED ROOF. SERVICE | | PLATFORM AND GUARDS | | 2017 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|