2019-07-19 16:38:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 020 - THERE ARE INCORRECT EDITIONS TO THE
 CURRENT FIRE CODES; NEC 2011 & FFPC 5TH EDITION
  
 THE CURRENT EDITION OF THE NEC IS 2014.
  
 THE FFPC IS THE 6TH EDITION WHICH INCLUDES THE 2015
 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND CORRECT.
  
  
  
  
 2) SHEET A 100 - THERE IS AN INDICATION OF A WALL
 CURTAIN WITHIN RM 119. THERE IS NO INDICATION IF IT
 WILL BE FIRE RETARDENT.
  
 FIRE RETARDENT IS REQUIRED DUE TO HIGH HAZARD AREA.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND A
 CERTIFICATE OF PROOF WHEN AVAILABLE.
  
  
  
 3) SHEET A 100 - THERE ARE TWO RETORTS INDICATED.
  
 THE INSTALLATION OF THE RETORTS SHALL COMPLY WITH NFPA
 86
  
 PER NFPA 86
  
 CHAPTER 1 ADMINISTRATION
 1.1* SCOPE. THIS STANDARD SHALL APPLY TO CLASS A, CLASS
 B, CLASS C,
 AND CLASS D OVENS, DRYERS, AND FURNACES; THERMAL
 OXIDIZERS; AND
 ANY OTHER HEATED ENCLOSURE USED FOR PROCESSING OF
 MATERIALS AND
 RELATED EQUIPMENT.
 1.1.1 THE TERMS OVENS, DRYERS, AND FURNACES ARE USED
 INTERCHANGEABLY
 AND SHALL ALSO APPLY TO OTHER HEATED ENCLOSURES
 USED FOR PROCESSING OF MATERIALS.
 1.1.2* WITHIN THE SCOPE OF THIS STANDARD, A CLASS A,
 CLASS B, OR
 CLASS C OVEN IS ANY HEATED ENCLOSURE OPERATING AT
 APPROXIMATELY
 ATMOSPHERIC PRESSURE AND USED FOR COMMERCIAL AND
 INDUSTRIAL PROCESSING OF MATERIALS.
 1.1.3 ACLASSAOVEN SHALL BE PERMITTED TO UTILIZE A
 LOW-OXYGEN
 ATMOSPHERE.
  
 PLEASE REVIEW AND PROVIDE THE TYPE PER NFPA AND THE
 RETORT SPECIFICATION SHEETS
  
  
  
 4) THERE ARE NO INDICATIONS OF THE VENTING SYSTEM FOR
 THE RETORTS.
  
 PER NFPA 86
  
 5.4.3 DUCTWORK.
 5.4.3.1 VENTILATING AND EXHAUST SYSTEMS, WHERE
 APPLICABLE,
 SHALL BE INSTALLED IN ACCORDANCE WITH CHAPTERS 1
 THROUGH 5 OF
 NFPA 91, STANDARD FOR EXHAUST SYSTEMS FOR AIR CONVEYING
 OF VAPORS,
 GASES, MISTS, AND NONCOMBUSTIBLE PARTICULATE SOLIDS,
 UNLESS OTHERWISE
 NOTED IN THIS STANDARD.
 5.4.3.2 WHEREVER FURNACE DUCTS OR STACKS PASS THROUGH
 COMBUSTIBLE
 WALLS, FLOORS, OR ROOFS, EITHER NONCOMBUSTIBLE
 INSULATION
 OR CLEARANCE, OR BOTH, SHALL BE PROVIDED TO PREVENT
 COMBUSTIBLE
 SURFACE TEMPERATURES FROM EXCEEDING 160?F (71?C).
  
 IF THE VENTING SYSTEM HAS TO BE DESIGNED OR INSTALLED
 SEPARATELY FROM THE RETORT, IT SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 5) SHEET FP 002 - THERE IS INDICATIONS OF UNDERGROUND
 FIRE LINE.
  
 UNDERGROUND FIRE LINE SHALL BE INSTALLED PER NFPA 24,
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS AND SEPARATE
 FORM FIRE SPRINKLER DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
  
 6) THERE ARE INDICATIONS OF AN EMERGENCY GENERATOR.
  
 THE GENERATOR SHALL BE SUBMITTED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS AND COMPLY WITH NEC, NFPA 37 AND NFPA
 110.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 7) SHEET E 201 - THE COOLER DOORS DO NOT APPEAR TO HAVE
 EXIT SIGNS OVER THE EXIT DOORS.
  
 THE ONE DOOR THAT DOES NOT HAVE THE ROLL DOWN FIRE DOOR
 SHOULD HAVE AN EXIT SIGN OVER IT.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL