2019-08-19 15:34:50 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19070081 |
| ADD: 5601 GREENWOOD AVE. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ?????????????????? |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 1ST REVIEW |
| DATE: MON. AUGUST 19/ 2019 |
| ACTION: DENIED |
| |
| 1) SHEET 004-A020 LIFE SAFETY PLAN UNDER THE HEADING |
| BUILDING DATA THE LINE FOR MIXED OCCUPANCY IS INDICATED |
| AS NO. THIS FLOOR PLAN DOES APPEAR TO BE A MIXED USE |
| BUILDING. IN THE 2017 FBC-B SECTION 509.3 AREA |
| LIMITATIONS. INCIDENTAL USES SHALL NOT OCCUPY MORE THAN |
| 10 % OF THE BUILDING AREA OF THE STORY IN WHICH THEY |
| ARE LOCATED. THE FLOOR PLAN INDICATES THE TOTAL UNDER |
| ROOF AREA IS 7,150 SQUARE FEET. FOR ANY OCCUPANCY OVER |
| 715 SQ. FT. THE BUILDING WOULD BE CONSIDERED MIXED USE. |
| BUSINESS THE COOLER STORAGE ARE OVER 715 SQ. FT. EACH |
| AND BOTH WOULD BE CONSIDERED SEPARATE OCCUPANCIES. |
| |
| 2) SHEET 008-A-100: |
| 2A) THERE ARE DISCREPANCIES IN THE REFERENCE FLOOR PLAN |
| AND THE DIMENSION PLAN. THE WALL SEPARATING THE |
| CREMATORY/ RECEIVING # 1 AND RECEIVING ROOM # 2 IS |
| SHOWN ON THE DIMENSION PLAN WITH WALL TYPES P4 & P7. A |
| 2 HOUR FIRE RATED WALL. WHEN YOU LOOK AT THE SEPARATING |
| THE CREMATORY FROM THE BUSINESS OCCUPANCY THE WALL P6 |
| IS SHOWN AS A 1 HOUR RATED WALL. THE DOOR SCHEDULE |
| SHEET A-500 SHOWS DOOR NUMBER 102 & 109 REQUIRING 90 |
| MINUTE OPENING PROTECTIVES AS WELL AS A 90 MINUTE ROLL |
| DOWN FIRE SHUTTER WITH FUSIBLE LINK. DISCREPANCY IN THE |
| HOUR RATING REQUIREMENT AND OPENING PROTECTIVE |
| REQUIREMENTS (FBC-B TABLE 716.5). |
| |
| 2B) THE SAME HOLD TRUE FOR THE WALLS SEPARATING THE |
| CREMATORY/ RECEIVING # 1 AND THE PROCESSING ROOM/ |
| ELECTRIC ROOM. THESE WALLS ARE IDENTIFIED WITH A WALL |
| TAG P6 (1 HOUR FIRE RATING) WHEREAS THE DOOR 120 IS |
| INDICATED IN THE DOOR SCHEDULE REQUIRING A 90 MINUTE |
| OPENING PROTECTIVE (FBC-B TABLE 716.5). DISCREPANCY |
| BETWEEN WALL AND OPENING PROTECTIVE RATINGS. |
| |
| 2C)(1) THE RECEIVING ROOM # 2 IS INDICATED IN HAVING A |
| WALL TYPE P3 & P8 BOTH BEING A 1 HOUR FIRE RATED WALL. |
| THE COMMON WALL WITH THE COOLER BEING A 1 HOUR RATED |
| WALL BUT THE DOOR INTO THE COOLER DOES NOT HAVE AN |
| IDENTIFICATION TAG, NOR A FIRE RATING. IT IS NOT CLEAR |
| IF THERE IS GOING TO BE A 45 MINUTE ROLL DOWN FIRE |
| SHUTTER OVER THIS OPENING. 107.21.2. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 2C)(2) PLEASE ALSO CONSIDER SECTION 1006.2.2.3. |
| 1006.2.2.3 REFRIGERATED ROOMS OR SPACES. ROOMS OR |
| SPACES HAVING A FLOOR AREA LARGER THAN 1,000 SQUARE |
| FEET CONTAINING A REFRIGERANT EVAPORATOR AND MAINTAINED |
| AT A TEMPERATURE BELOW 68?F, SHALL HAVE ACCESS TO NOT |
| LESS THAN TWO EXITS OR EXIT ACCESS DOORWAYS. |
| |
| 3A) SHEET 008-A-100 WALL LEGEND. IN EACH OF THE WALL |
| DETAILS THAT SHOW A FIRE RATED WALL THE DETAILS STATE |
| THE STUD GAUGE IS TO BE A 22 GAUGE METAL STUD (MSG). IN |
| EACH OF THE UL LISTING GIVEN THEY ALL LISTED A 20 GAUGE |
| METAL STUD AS THE REQUIRED GAUGE OF STUD. PLEASE ALSO |
| CLARIFY SINCE THERE 2 TYPES OF 20 GAUGE STUDS. |
| DRYWALL AND A MINIMUM THICKNESS (MILLS) OF 30 AND 20 |
| GAUGE STRUCTURAL AND MINIMUM THICKNESS OF 33 (MILLS). |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3B) PLEASE ALSO CONSIDER THE METAL STUD WALLS WHERE THE |
| FIRE SHUTTERS ARE GOING TO BE INSTALLED. SHEET A601 |
| INDICATES THAT A MINIMUM OF 16 GAUGE STRUCTURAL STEEL |
| STUDS ARE REQUIRED TO INSTALL THE ROLLING COUNTER FIRE |
| DOOR. |
| |
| 4) WALK-IN COOLERS REQUIRE THEIR OWN PERMIT, REVIEW AND |
| ASSOCIATED FEES. INFORMATIONAL. |
| |
| 5) SHEET 014-A300 SECTION 1 SHOWS THE USE OF 2 LAYERS |
| OF 2 INCH THICK RIGID INSULATION BELOW THE SLAB. |
| TERMITES WILL BE A BIG PROBLEM WITH THE INSULATION |
| UNDER THE CONCRETE SLAB. PLEASE REFER TO THE 2017 FBC-B |
| 2603.8 PROTECTION AGAINST TERMITES. IN FLORIDA, |
| EXTRUDED AND EXPANDED POLYSTYRENE, POLYISOCYANURATE AND |
| OTHER FOAM PLASTICS SHALL NOT BE INSTALLED ON THE |
| EXTERIOR FACE OR UNDER INTERIOR OR EXTERIOR FOUNDATION |
| WALLS OR SLAB FOUNDATIONS LOCATED BELOW GRADE. |
| EXCEPTIONS: |
| 1. BUILDINGS WHERE THE STRUCTURAL MEMBERS OF WALLS, |
| FLOORS, CEILINGS, ROOFS AND ROOF ASSEMBLIES (TRUSSES) |
| ARE ENTIRELY OF NONCOMBUSTIBLE MATERIALS OR |
| PRESERVATIVE-TREATED WOOD. |
| 2. AN APPROVED METHOD OF PROTECTING THE FOAM PLASTIC |
| AND STRUCTURE FROM SUBTERRANEAN TERMITE DAMAGE IS |
| PROVIDED. |
| |
| 6) SHEET A400 THE BREAK ROOM SINK THE COUNTERTOP DOES |
| NOT HAVE THE HEIGHT FROM THE FINISH FLOOR. 2017 |
| FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES |
| AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE |
| HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 7) SHEET A401 DETAILS 2A & 2B SHOW THE GRAB BAR BEING |
| MEASURED FROM THE CENTERLINE OF THE GRAB BAR NOT THE |
| TOP OF THE GRASPABLE SURFACE. 2017 FBC-ACCESSIBILITY |
| CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS |
| SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT |
| CENTERLINE. |
| |
| 8) NOTICE ONLY. TRUSS LAYOUT AND ENGINEERING SHEETS ARE |
| TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF RECORD, |
| SHOP DRAWING STAMP OF APPROVAL AFFIXED BEFORE BEING |
| SUBMITTED TO THE BUILDING DEPARTMENT. |
| |
| 9) S2.1 ROOF FRAMING PLAN & M201 MECHANICAL ROOF PLAN |
| BOTH SHOW ROOF TOP MECHANICAL UNITS BUT NO DETAILS AS |
| TO HOW THE CURB IS TO BE ANCHORED TO THE ROOF FRAMING |
| AND HOW THE RTU IS TO BE ANCHORED TO THE ROOF TOP CURB. |
| LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 10) SHEET M201 NOTE # 7 MECHANICAL CONTRACTOR TO SUPPLY |
| ROOF TOP STANDS FOR COOL CELL CONDENSER. THE ROOF TOP |
| A/C STAND PRODUCT APPROVAL WILL NEED TO BE SUBMITTED, |
| REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| 11A) SHEET A300 & A301 DETAIL 2 BOTH SHOW THE |
| MECHANICAL EQUIPMENT ON THE FLAT ROOFED AREA WITH THE |
| ROOF ELEVATION AT 17 FEET A. F. F. PLEASE SHOW HOW |
| COMPLIANCE WILL BE ACHIEVED FOR ACCESS TO THE ROOF TOP |
| EQUIPMENT. |
| 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS |
| OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES |
| REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED |
| STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 MM), |
| SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED |
| MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM |
| GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? |
| LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE |
| CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH |
| OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS |
| VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| |
| 11B) IF ROOF TOP ACCESS HATCH IS TO BE USED PLEASE |
| COMPLY WITH THE SIZE REQUIREMENTS. FBC-B 1011.12.2. |
| ROOF ACCESS, EXCEPTION: IN BUILDINGS WITHOUT AN |
| OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE PERMITTED TO |
| BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE |
| FEET IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET. |
| |
| 12) THE INDEX SHEET INDICATES VARIOUS PRODUCT |
| APPROVALS, THEY CAN BE DEFERRED UNTIL AFTER PERMIT |
| ISSUANCE. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 13) REQUIRED PRODUCT APPROVALS: 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 14) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 15) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| THE SUBMITTED REPORT NEMO REPORT HAS OVER 100 PAGES OF |
| SUB-SYSTEMS AND ASSOCIATED PRESSURES, SOME CAN HAVE |
| ENHANCED FASTENING AND SOME CANNOT. PLEASE IDENTIFY |
| WHICH SUB-SYSTEM IS TO BE INSTALLED. |
| |
| 16) IMPACT FEES - DIGITAL SUBMITTALS: |
| PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| |
| 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| |
| |
| |
| |
| |
| |
| |