2019-10-21 13:01:55ELECTRICAL PLAN REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM
 UTILITY.
  
 2. RISER DIAGRAM SHOWS AN INSTALLATION THAT IS NOT CODE
 COMPLIANT. MAINS NEEDS TO BE GROUPED. PROVIDE
 CORRECTION. NEC 230.72; FBC RE 3601.6.
  
 3. PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL
 LOADS FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS
 FOR THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
 4. OK
  
 5. OK
 6. OK
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  