2019-10-21 13:01:55 | ELECTRICAL PLAN REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 | | | | PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM | | UTILITY. | | | | 2. RISER DIAGRAM SHOWS AN INSTALLATION THAT IS NOT CODE | | COMPLIANT. MAINS NEEDS TO BE GROUPED. PROVIDE | | CORRECTION. NEC 230.72; FBC RE 3601.6. | | | | 3. PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL | | LOADS FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS | | FOR THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2. | | | | 4. OK | | | | 5. OK | | 6. OK | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | PHIL PETTY | | 561-644-7305 | | |
|