2019-07-30 09:38:53 | ELECTRICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| |
| PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM |
| UTILITY. |
| |
| 2. RISER DIAGRAM SHOWS AN INSTALLATION THAT IS NOT CODE |
| COMPLIANT. MAINS NEEDS TO BE GROUPED. PROVIDE |
| CORRECTION. NEC 230.72; FBC RE 3601.6. |
| |
| 3. PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL |
| LOADS FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS |
| FOR THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2. |
| |
| 4. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUT. NEC 250; FBC RE 3607.3. |
| |
| 5. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED IN ADDITION TO THE MAIN GROUPED PER |
| COMMENT # 2 ABOVE. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR THE DETACHED GARAGE PER |
| NEC 225.31 & 225.32. |
| |
| 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |