2019-10-09 06:39:29 | PLUMBING 2ND REVIEW**DENIED** |
| |
| 1) 2ND REQUEST. THE LOUNGE HAS A REQUIRED TOILET ROOM. |
| FBC-PLB 403.2 CLEARLY STATES WHERE PLUMBING FIXTURES |
| ARE REQUIRED A SEPARATE FACILITY SHALL BE PROVIDED FOR |
| EACH SEX. THIS COMMENT REMAINS. |
| 2) 2ND REQUEST. THE MAINTENANCE ROOM BREAK SINK SHALL |
| COMPLY WITH FBC-ACC 606.3, 804, 804.3.2. SINK TOP MAX |
| SHALL BE NO MORE THEN 34?. |
| 3) SHT. A-5.8 AND 5.10 DETAIL B AND D STILL SHOW THE |
| GRAB BAR MOUNTING TO BE CENTERED OF THE BAR. |
| MEASUREMENT SHALL BE TO THE TOP OF THE GRIPPING |
| SURFACE. FBC-ACC 609.4 |
| 4) SHT. A 5.10 SHOW ALL MIRROR MOUNTING TO THE BOTTOM |
| EDGE. MIRROR MEASUREMENT SHALL BE TAKEN @ THE |
| REFLECTIVE SURFACE OF THE GLASS. FBC-ACC 603.3 |
| 5) PROVIDE LOCATION OF ACCESSIBLE SHUT OFF VALVES FOR |
| THE WASHER BOX SINCE IT APPEARS THE STACKABLE WASHER |
| AND DRYER WILL BE BLOCKING READY ACCESS TO THE BOX SHUT |
| OFF VALVES. FBC-PLB 606.3 |
| 6) REMOVE NOTE 2.4.1 ON SHT. P-6.2. 3M PIP WRAP IS NOT |
| PERMITTED IN THE CITY OF WEST PALM BEACH. ALL CPVC |
| PIPING IN AIR RETURN SHALL MEET THE 25/50 SMOKE INDEX |
| RATING. |
| 7) SHT. P6.3 SHOW THE TEMPERING VALVE AS AN APPROVED |
| ASSE 1070 VALVE ON DETAIL #5 |
| 8) ADD NOTE TO PLANS THE GREASE INTERCEPTOR AND |
| BACKFLOWS REQUIRED SEPARATE PERMIT. ALL BACKFLOW ARE |
| REQUIRED TO BE INSTALLED BY A LICENSE PLUMBER ONLY. FL |
| STATUTE 489, 2017 W.P.B CROSS CONNECTION MANUAL. |
| |
| |