2019-08-22 14:49:54 | 1ST REVIEW: 19061385 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1.SEPARATE FACILITIES ARE REQUIRED FOR THE LOUNGE ON |
| THE 4TH FLOOR. PER FBC PL 403.2 SEPARATE |
| FACILITIES.WHERE PLUMBING FIXTURES ARE REQUIRED, |
| SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. |
| |
| 2. SHT. A5.3 LABEL CLEAR FLOOR SPACE FOR THE TOILETS, |
| LAVATORY'S AND WATER FOUNTAIN. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 3. SHT. A.5.8 DETAIL #1 SHOW CLEAR FLOOR SPACE WITH |
| DIMENSIONS FOR THE TOILET AND LAVATORY. PER FBC ACC |
| 604.3.1, 606.2 |
| |
| 4. THE SINK IN THE MAINTENANCE ROOM SHALL COMPLY WITH |
| FBC ACC 606.2, 606.3, 212.3 |
| |
| 5. SHT. A.5.10 LABEL CLEAR FLOOR SPACE FOR THE TOILETS, |
| LAVATORY'S AND WATER FOUNTAIN. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 6. ALL GRAB BARS SHALL BE SHOWN TO BE MEASURED TO THE |
| TOP OF THE GRIPPING SURFACE FROM FINISHED FLOOR. PER |
| FBC ACC 609.4 |
| |
| 7. A URINAL IS REQUIRED IN THE MENS BATHROOM SERVING |
| THE POOL AREA PER FBC PL 403.6 |
| |
| 8. SHT. A10.1-3 SHOW THE MAX DEPTH OF THE VANITY'S AT |
| 24 IN. PER FHADM PG 7.43 |
| |
| 9. SHT. A10.4 THE DETAILS SHOWING THE CLEAR FLOOR SPACE |
| AT THE LAVATORY'S IS SHOWING THE DEPTH OF THE VANITY AT |
| 25IN. IT SHALL BE MAX OF 24IN.PER FHADM PG 7.43 |
| |
| 10. PROVIDE DETAIL FOR OVERFLOW SCUPPER WITH |
| DIMENSIONS. PER WPB AMEND TO FBC 107.2.1, FBC PL 1108.3 |
| |
| 11. SHT. P-5.6 LABEL OVERFLOW SCUPPERS. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 12. PLEASE PROVIDE MANUFACTURE INSTILLATION GUIDE FOR |
| GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| |
| 13. SHT. P-6.1 DETAIL #1 AIR CHAMBERS ARE NOT APPROVED |
| IT SHALL BE WATER-HAMMER ARRESTOR SHALL CONFORM TO ASSE |
| 1010 . PER FBC PL 604.9 |
| |
| 14. PROVIDE DETAIL FOR TRASH SHUT WASH RING SHALL BE |
| EQUIP WITH BACK FLOW DEVICE. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 15. SHT. P-5.4-5 THE ISOMETRIC DRAWING ARE TO COMPACT |
| TO DETERMINE CODE COMPLIANCE PLEASE SEPARATE AND |
| ENLARGE. PER WPB AMEND TO FBC 107.2.1 |
| |
| 16. THE SINK BEHIND POOL EQUIPMENT ROOM IS MISSING FROM |
| SANITARY ISOMETRIC.PER WPB AMEND TO FBC 107.2.1 |
| |
| 17.AUTOMATIC AIR ADMITTANCE VALVE IN THE POOL EQUIPMENT |
| ROOM CAN NOT BE INSTALLED ON GROUND FLOOR THEY ARE NOT |
| APPROVED FOR INSTILLATION BELOW FOUR FLOORS. PER FBC PL |
| 918.3.1 |
| |
| 18. PROVIDE MANUFACTURE SPECIFICATION SHEET FOR SUB |
| METER SHALL BE FIRE RATED FOR USE IN AIR PLENUM. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 19. PROVIDE DETAIL FOR THERMAL EXPANSION VALVE AND SHOW |
| LOCATION ON OVERALL WATER ISOMETRIC DRAWING.PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 20. THE WATTS 530-C RELIEF VALVE IS NOT APPROVED FOR A |
| LARGE SYSTEM LIKE THIS IF YOU USING A SINGLE VALVE OR |
| TANK FOR THE WHOLE SYSTEM PLEASE PROVIDE MANUFACTURE |
| SPECIFICATIONS THAT SHOW IT IS DESIGNED FOR A SYSTEM |
| THE LARGE AND SHALL BE LEAD FREE. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
2019-07-25 11:41:49 | CHECK WATER TO FOUNTAINS IN DOG PARK AND CONFLICT WITH |
| WATER PIPE AND BENCH IN DOG PARK. |