2019-08-20 07:57:15 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19061385 |
| 8/19/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS M2.1A: THE 12X8 DUCT PENETRATION INTO THE |
| STAIR #4 ENCLOSURE AND EXIT PASSAGEWAY IS PROHIBITED- |
| SEE SECTIONS 1023.5 & 1023.6 FBC B. |
| 2) M2.1A, M21.B: THERMOSTATIC CONTROLS ARE REQUIRED FOR |
| THE MINI SPLIT SYSTEMS IN THE TRASH ROOMS, MAINTENANCE |
| ROOMS, AND ELECTRICAL ROOMS ETC.- SEE SECTION |
| C403.2.4.1 FBC EC. |
| 3) M2.1A & M2.1B: INDEPENDENT VENTILATION OR AIR |
| CONDITIONING SYSTEMS ARE REQUIRED FOR ELEVATOR MACHINE |
| ROOMS OR SPACES PER SECTION 3005.2 FBC B. IT APPEARS |
| THAT THE ELEVATORS SHOWN ON THE PLAN HAVE EQUIPMENT |
| LOCATED IN THE HOISTWAYS. CLARIFY HOW COMPLIANCE WILL |
| BE MET. |
| ELEVATOR MACHINE ROOMS, MACHINERY SPACES THAT CONTAIN |
| THE DRIVING MACHINE, AND CONTROL ROOMS OR SPACES THAT |
| CONTAIN THE OPERATION OR MOTION CONTROLLER FOR ELEVATOR |
| OPERATION SHALL BE PROVIDED WITH AN INDEPENDENT |
| VENTILATION OR AIR-CONDITIONING SYSTEM TO PROTECT |
| AGAINST THE OVERHEATING OF THE ELECTRICAL EQUIPMENT. |
| THE SYSTEM SHALL BE CAPABLE OF MAINTAINING TEMPERATURES |
| WITHIN THE RANGE ESTABLISHED FOR THE ELEVATOR |
| EQUIPMENT. |
| 4) M.21A & M2.1B: PROVIDE CONDENSATE DISPOSAL PLANS FOR |
| THE COMMON AREA AND ROOM AC SYSTEMS -LOUNGE, LOBBY, |
| WELLNESS, FITNESS- AND THE MINI SPLIT SYSTEMS |
| CONDITIONING THE TRASH ROOMS, MAINTENANCE ROOMS, |
| ELECTRICAL ROOMS, AND IT ROOMS- SECTION 307.2 FBC M. |
| 5) M.2.1B: PROVIDE ENLARGED POOL EQUIPMENT ROOM |
| DRAWINGS AND SPECIFICATIONS. IDENTIFY ALL EQUIPMENT IN |
| THE ROOM, AND WHAT CHEMICALS WILL BE STORED IN THE ROOM |
| AND THEIR QUANTITIES. PROVIDE AN INDEPENDENT EXHAUST |
| VENTILATION SYSTEM FOR THE ROOM AND ALL REQUIRED LOCAL |
| EXHAUST SYSTEMS FOR EQUIPMENT- SECTION 107.2.1 WPB. |
| PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR WHEN |
| MORE INFORMATION IS PROVIDED. |
| 6) M.3.1: SHOW THE LOCATION OF THE THERMOSTAT FOR THE |
| LOUNGE AC SYSTEM- SECTION C403.2.4.1 FBC EC. |
| 7) M.4.1: MOTORIZED DAMPERS IN THE DRYER EXHAUST DUCT |
| RUNS ARE MISTAKENLY SHOWN IN UNITS A2 & A3, AND SHOULD |
| BE RELOCATED TO THE O/A INTAKE DUCTS- SEE SECTIONS |
| 504.4 FBC M, AND SECTION C403.2.4.3 FBC EC. |
| 8) M.4.2: PLACE THE CORRELATING KEY NOTES ON THE PLAN- |
| SECTION 107.2.1 WPB. |
| 9) M.4.1, M.4.2, AND M.5.1: THE APPLICATION OF |
| INTUMESCENT PAINT TO THE AC CLOSET DOORS MUST BE |
| CERTIFIED BY THE PAINT MANUFACTURER IN ACCORDANCE WITH |
| THEIR SPECIFICATIONS, OR BY THE ENGINEER OF RECORD- |
| SECTION 107.2.1 WB. PLEASE PLACE NOTE(S) ON THE PLANS |
| TO INDICATE HOW COMPLIANCE WILL BE MET. |
| 10) SHOW ALL REQUIRED CLEARANCES FOR THE O/A INTAKES |
| INTO THE BUILDING AND APARTMENTS PER SECTION 401.4 FBC |
| M. VERIFY 10? CLEARANCES TO THE PROPERTY LINES ON ALL |
| SIDES OF THE BUILDING. |
| 11) SEPARATE PERMITS ARE REQUIRED FOR THE FUTURE RETAIL |
| AND RESTAURANT HVAC SYSTEMS, KITCHEN HOODS AND FIRE |
| SUPPRESSION SYSTEMS, AND WALK-IN COOLERS AND FREEZERS- |
| SECTION 107.1 WPB. PLEASE PLACE NOTES ON THE PLAN. |
| 12) DEFERRED SUBMITTALS: THE FOLLOWING LIST OF |
| MECHANICAL EQUIPMENT AND DEVICES MAY BE SUBMITTED TO |
| THE BUILDING DEPARTMENT FOR REVIEW OR BE ONSITE AT TIME |
| OF INSPECTION. PLEASE PROVIDE A MASTER LIST ON THE PLAN |
| THAT INCLUDES THE ITEMS BELOW AND ANY ADDITIONAL |
| REQUIRED. |
| 1) MIAMI-DADE NOA?S AND/OR FLORIDA PRODUCT APPROVALS |
| FOR AC STANDS, RTU CURBS, LOUVERS. |
| 2) FIRE AND FIRE/SMOKE DAMPERS. |
| 3) DUCT SMOKE DETECTORS. |
| 4) MOTORIZED O/A DAMPERS. |
| 5) CLOTHES DRYERS. |
| 6) KITCHEN COOKING APPLIANCES |
| 7) RECIRCULATING RANGE HOODS |
| 8) WATER HEATERS. |
| 9) X-VENT WALL CAPS. |
| 10) WIND LOAD ENGINEERING FOR ANCHORING ALL MECHANICAL |
| EQUIPMENT AND APPLIANCES. |
| 11) COMMISSIONING AND TEST AND BALANCE REPORTS. |
| 12) INTUMESCENT DOOR PAINT CERTIFICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |