2019-08-20 07:57:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19061385
 8/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.1A: THE 12X8 DUCT PENETRATION INTO THE
 STAIR #4 ENCLOSURE AND EXIT PASSAGEWAY IS PROHIBITED-
 SEE SECTIONS 1023.5 & 1023.6 FBC B.
 2) M2.1A, M21.B: THERMOSTATIC CONTROLS ARE REQUIRED FOR
 THE MINI SPLIT SYSTEMS IN THE TRASH ROOMS, MAINTENANCE
 ROOMS, AND ELECTRICAL ROOMS ETC.- SEE SECTION
 C403.2.4.1 FBC EC.
 3) M2.1A & M2.1B: INDEPENDENT VENTILATION OR AIR
 CONDITIONING SYSTEMS ARE REQUIRED FOR ELEVATOR MACHINE
 ROOMS OR SPACES PER SECTION 3005.2 FBC B. IT APPEARS
 THAT THE ELEVATORS SHOWN ON THE PLAN HAVE EQUIPMENT
 LOCATED IN THE HOISTWAYS. CLARIFY HOW COMPLIANCE WILL
 BE MET.
 ELEVATOR MACHINE ROOMS, MACHINERY SPACES THAT CONTAIN
 THE DRIVING MACHINE, AND CONTROL ROOMS OR SPACES THAT
 CONTAIN THE OPERATION OR MOTION CONTROLLER FOR ELEVATOR
 OPERATION SHALL BE PROVIDED WITH AN INDEPENDENT
 VENTILATION OR AIR-CONDITIONING SYSTEM TO PROTECT
 AGAINST THE OVERHEATING OF THE ELECTRICAL EQUIPMENT.
 THE SYSTEM SHALL BE CAPABLE OF MAINTAINING TEMPERATURES
 WITHIN THE RANGE ESTABLISHED FOR THE ELEVATOR
 EQUIPMENT.
 4) M.21A & M2.1B: PROVIDE CONDENSATE DISPOSAL PLANS FOR
 THE COMMON AREA AND ROOM AC SYSTEMS -LOUNGE, LOBBY,
 WELLNESS, FITNESS- AND THE MINI SPLIT SYSTEMS
 CONDITIONING THE TRASH ROOMS, MAINTENANCE ROOMS,
 ELECTRICAL ROOMS, AND IT ROOMS- SECTION 307.2 FBC M.
 5) M.2.1B: PROVIDE ENLARGED POOL EQUIPMENT ROOM
 DRAWINGS AND SPECIFICATIONS. IDENTIFY ALL EQUIPMENT IN
 THE ROOM, AND WHAT CHEMICALS WILL BE STORED IN THE ROOM
 AND THEIR QUANTITIES. PROVIDE AN INDEPENDENT EXHAUST
 VENTILATION SYSTEM FOR THE ROOM AND ALL REQUIRED LOCAL
 EXHAUST SYSTEMS FOR EQUIPMENT- SECTION 107.2.1 WPB.
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR WHEN
 MORE INFORMATION IS PROVIDED.
 6) M.3.1: SHOW THE LOCATION OF THE THERMOSTAT FOR THE
 LOUNGE AC SYSTEM- SECTION C403.2.4.1 FBC EC.
 7) M.4.1: MOTORIZED DAMPERS IN THE DRYER EXHAUST DUCT
 RUNS ARE MISTAKENLY SHOWN IN UNITS A2 & A3, AND SHOULD
 BE RELOCATED TO THE O/A INTAKE DUCTS- SEE SECTIONS
 504.4 FBC M, AND SECTION C403.2.4.3 FBC EC.
 8) M.4.2: PLACE THE CORRELATING KEY NOTES ON THE PLAN-
 SECTION 107.2.1 WPB.
 9) M.4.1, M.4.2, AND M.5.1: THE APPLICATION OF
 INTUMESCENT PAINT TO THE AC CLOSET DOORS MUST BE
 CERTIFIED BY THE PAINT MANUFACTURER IN ACCORDANCE WITH
 THEIR SPECIFICATIONS, OR BY THE ENGINEER OF RECORD-
 SECTION 107.2.1 WB. PLEASE PLACE NOTE(S) ON THE PLANS
 TO INDICATE HOW COMPLIANCE WILL BE MET.
 10) SHOW ALL REQUIRED CLEARANCES FOR THE O/A INTAKES
 INTO THE BUILDING AND APARTMENTS PER SECTION 401.4 FBC
 M. VERIFY 10? CLEARANCES TO THE PROPERTY LINES ON ALL
 SIDES OF THE BUILDING.
 11) SEPARATE PERMITS ARE REQUIRED FOR THE FUTURE RETAIL
 AND RESTAURANT HVAC SYSTEMS, KITCHEN HOODS AND FIRE
 SUPPRESSION SYSTEMS, AND WALK-IN COOLERS AND FREEZERS-
 SECTION 107.1 WPB. PLEASE PLACE NOTES ON THE PLAN.
 12) DEFERRED SUBMITTALS: THE FOLLOWING LIST OF
 MECHANICAL EQUIPMENT AND DEVICES MAY BE SUBMITTED TO
 THE BUILDING DEPARTMENT FOR REVIEW OR BE ONSITE AT TIME
 OF INSPECTION. PLEASE PROVIDE A MASTER LIST ON THE PLAN
 THAT INCLUDES THE ITEMS BELOW AND ANY ADDITIONAL
 REQUIRED.
 1) MIAMI-DADE NOA?S AND/OR FLORIDA PRODUCT APPROVALS
 FOR AC STANDS, RTU CURBS, LOUVERS.
 2) FIRE AND FIRE/SMOKE DAMPERS.
 3) DUCT SMOKE DETECTORS.
 4) MOTORIZED O/A DAMPERS.
 5) CLOTHES DRYERS.
 6) KITCHEN COOKING APPLIANCES
 7) RECIRCULATING RANGE HOODS
 8) WATER HEATERS.
 9) X-VENT WALL CAPS.
 10) WIND LOAD ENGINEERING FOR ANCHORING ALL MECHANICAL
 EQUIPMENT AND APPLIANCES.
 11) COMMISSIONING AND TEST AND BALANCE REPORTS.
 12) INTUMESCENT DOOR PAINT CERTIFICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  