2019-07-01 11:16:58 | 1ST REVIEW: 19061348 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. THE REVISIONS TO THE MASTER OR UNDER THE APPROVED |
| MASTER PERMIT SHALL BE SIGNED AND SEALED BY DESIGN |
| PROFESSIONAL OF RECORD DAVID LAWRENCE. PER WPB AMEND TO |
| FBC 107.2.1 /61G15-23.001, F.A.C |
| |
| 2. THE FLOOR PLAN DOES NOT MATCH APPROVED PLAN AFTER |
| CHECKING INSPECTION NOTES IT APPEARS THAT A FULL |
| REVISION IS GOING TO BE REQUIRED, THE GAS REVISION |
| FLOOR PLAN SHALL MATCH APPROVED PLAN . PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS SEC. |
| 402.2 |
| |
| 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2017 FUEL GAS CODE SEC. 304. |
| |
| 5. THE FIRST TABLE LISTED 402.4(5) IS LABELED |
| CORRUGATED STAINLESS STEEL TUBING (CSST)THIS DOESN'T |
| MATCH THE CODE IT SHALL BE SCH 40 METALLIC PLEASE LIST |
| CORRECT TABLE FOR PIPE BEING INSTALLED.PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 6. ON REGULATOR A YOU LIST 937,000 BTU WHEN I ADDED THE |
| BTU LOADS ON THE RISER IT ADDS UP TO 947,000 BTU PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7. THE SECTION OF PIPE BETWEEN THE GENERATOR IS |
| UNDERSIZED IT SHOULD BE 11/2 PER TABLE 402.4(2) AT 50FT |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |