2019-06-27 10:59:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS INSUFFICIENT DETAILS PROVIDED TO DETERMINE |
| COMPIANCE WITH THE LIFE SAFETY CODE. |
| |
| |
| |
| 2) THIS IS A PARKING GARAGE CLASSIFIED AS A STORAGE |
| OCCUPANCY. THE PROPOSED EVENT IS AN ASSEMBLY EVENT. |
| |
| 2A) WHAT IS THE PROPOSED ATTENDANCE? |
| |
| 2B) HOW WILL THE ATTENDANCE BE MONITORED/MAINTAINED? |
| (TO PREVENT OVERCROWDING OF THE ROOF TOP) |
| |
| 2C) PROVIDE THE DIMENSIONS OF THE OPEN SPACES AS THIS |
| AREA IS THE ASSEMBLY AREA AND THE OCCUPANCY LOAD CAN |
| NOT BE EXCEED. |
| |
| |
| |
| 3) ARE TENTS BEING USED, PLEASE PROVIDE THOSE |
| LOCATIONS. |
| |
| |
| |
| 4) BBQ IS INDICATED. WHAT IS THE AREA OF BBQ, HOW MANY, |
| WHAT TYPE? |
| |
| SHALL BE A MINIMUM OF 10' AWAY FROM ALL COMBUSTILES AND |
| VENT TO THE OPEN AIR (UNDER NO CEILING AREA OR LOWER |
| LEVELS) |
| |
| 4A) A MIINIMUM 2A,10BC FIRE EXTINGUISHER SHALL BE |
| LOCATED WITH EACH SEPARATE BBQ. |
| |
| |
| |
| 5) A STAGE IS INDICATED, IS IS ROLL OUT TYPE OR IS IT |
| BUILT ON SITE? |
| |
| 5A) WHAT IS STAGE CONSTRUCTION TYPE? |
| |
| |
| 6) HOW WILL POWER BE SUPPLIED TO THIS EVENT, |
| GENERATOR/EXTENSION CORDS? |
| |
| 6A) PROVIDE GENERATOR LOCATIONS, IF APPLICABLE. |
| |
| 6B) EXTENSION CORDS SHALL BE PROTECTED FROM TRIP HAZARD |
| AND ACCIDENTAL DAMAGE. |
| |
| PROVIDE DETAILS. |
| |
| |
| |
| 7) THERE SHALL BE NO PYROTECHINCS OR FIREWORKS FROM |
| THIS STAGE OR ROOF TOP EVENT. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |