2019-07-18 09:18:57 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19061299 |
| 7/18/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M0.1: THE O/A CALCULATIONS ARE BASED ON RATES |
| FOR OFFICES HOWEVER THE PLANS ARE INDICATING THE TENANT |
| SPACES ARE "STUDIOS". PLEASE CLARIFY WHAT TYPES OF |
| STUDIOS THESE ARE.TABLE 403.3.1.1 DOES NOT PROVIDE A |
| VENTILATION IN GENERAL FOR STUDIOS, HOWEVER THERE ARE |
| RATES LISTED FOR PHOTO STUDIOS, THEATER STUDIOS, AND |
| ART CLASSROOMS. PLEASE SEE SECTION 403.3.1.1 AND |
| PROVIDE THE RATES THAT ARE MOST SIMILAR TO WHAT THE USE |
| AND FUNCTIONS OF THESE SPACES WILL BE. |
| |
| 2) M1.1 & M1.2: PROVIDE EITHER NOTES OR MEASUREMENTS ON |
| THE PLAN TO INDICATE THE LOCATIONS OF THE O/A INLETS |
| ARE IN COMPLIANCE WITH SECTION 401.4 FOR REQUIRED |
| CLEARANCES. |
| |
| 3) M2.1 & M2.2: PROVIDE A DETAIL FOR ATTACHING THE NEW |
| CU'S TO THE EXISTING STANDS- SECTION 301.15 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |