2020-03-02 18:40:38PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SOME OF THE INFORMATION PROVIDED IN THE INSTALLATION
 SCHEDULE APPEARS TO BE INCORRECT. FBC 107.2.1
 A) THE SHUTTER SPANS SHOULD BE MORE THAN THE OPENING
 HEIGHT BASED ON THE EDGE DISTANCE REQUIREMENTS. PLEASE
 CORRECT.
 B) BASED ON THE POURED CONCRETE ANCHOR SPACING SCHEDULE
 ON SHEET 12, THE SPACING OF THE ANCHORS FOR WALL HEADER
 MOUNTING "A" AND WALL SILL MOUNTING "D" IS 10" FOR A
 NEGATIVE DESIGN LOAD OF 60 PSF. YOU USE NEGATIVE 60 PSF
 BECAUSE THE WALL PRESSURE FOR THE OPENINGS IS MORE THAN
 40 PSF AND 60 PSF IS THE NEXT HIGHER PRESSURE ON THE
 SCHEDULE. PLEASE CORRECT.
  