2019-07-08 08:39:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY C. THE
 COMPONENT AND CLADDING PRESSURES AND THE EXPOSURE
 CATEGORY LISTED ON THE FORM THAT WAS SUBMITTED IS
 EXPOSURE CATEGORY B. IN ORDER TO USE EXPOSURE B, YOU
 WILL NEED TO PROVIDE A SITE SPECIFIC ANALYSIS SHOWING
 THAT THIS PROPERTY IS ACTUALLY EXPOSURE CATEGORY B. THE
 ANALYSIS IS REQUIRED TO BE PRODUCED BY AND SIGNED AND
 SEALED BY A FLORIDA LICENSED PROFESSIONAL ENGINEER. FBC
 107.2.1 & FS 471
  
 2) THE MEAN ROOF HEIGHT FOR THIS BUILDING IS 25 FEET
 PER THE INFORMATION THAT YOU PROVIDED. YOU NEED TO USE
 THE MEAN ROOF HEIGHT OF THE BUILDING FOR DETERMINING
 THE COMPONENT AND CLADDING PRESSURES FOR THE SHUTTERS.
 FBC R301.2.1
  
 FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN INSTALLATION
 SCHEDULE AND KEY PLAN FOR THE STORM PANELS. SPECIFY THE
 OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR,
 ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL
 SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE
 APPLICABLE SECTION NUMBER FROM THE INSTALLATION
 DRAWINGS. I HAVE INCLUDED A LINK TO THE CONSTRUCTION
 SERVICES DEPARTMENT SITE THAT HAS MANY OF THE RELATED
 FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  