2019-07-26 17:49:01 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE |
| NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON |
| SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER. |
| |
| ALL POINTS SOLID SET REQUIRES A 3.5" EDGE DISTANCE, OR |
| A FACTOR OF .78 FOR AN EDGE DISTANCE OF 3". |
| FASTENER PROPOSED IS NOT CLEAR; THE INSTALLATION |
| SPECIFIES ALL POINTS SOLID SET AND TAPCON. SEE PREVIOUS |
| LIST, YOU NEED TO STATE WHICH TAPCON (SEE CHART ON PAGE |
| 13). |
| |
| THE SPAN IS NOT CLEAR; FOR INSTANCE OPENING 2 IS 74 X |
| 74, BUT SPAN IS 148. SPAN SHOULD BE BLADE LENGTH. |
| |
| SHUTTER MOUNTING TYPE SHOULD CORRELATE WITH THE ANCHOR |
| CHARTS (SEE 12, 13; ANCHOR CONNECTION TYPES ARE NAMED |
| A, C, D, H, ETC.). |
| |
| EXPOSURE SHOULD BE C (NOT B); PRESSURES APPEAR TOO LOW. |
| IF PRESSURES ARE LOWER THAN FBC R TABLE 301.2(2), |
| CALCULATIONS OR ENGINEERING WILL BE REQUIRED. UPON |
| REQUEST THE DESIGN PRESSURES WILL BE SENT TO YOU VIA |
| EMAIL. |
| |
| 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| |
| |
| |
| |