Plan Review Notes
Plan Review Notes For Permit 19061197
Permit Number 19061197
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-28 11:09:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO
 DETERMINE COMPLIANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 GREATER DETAIL IS REQUIRED INCLUDING SIZE OF OPENING,
 HORIZONTAL VIEWS, INSIDE AND OUTSIDE, ETC.
  
  
  
 2) A DOOR IS PROPOSED TO BE REMOVED. THERE ARE NO
 INDICATIONS IF THIS IS A REQUIRED EXIT DOOR, PER NFPA
 101, CH 7 MEANS OF EGRESS.
  
 A MINIMUM OF TWO EXITS ARE REQUIRED AND ONE CAN NOT
 HAVE PATRONS EXITING THROUGH THE KITCHEN AREA.
  
 A DETAILED LIFE SAFETY PLAN IS REQUIRED SHOWING
 COMPLIANCE WITH REQUIRED EXITING IN COMPLIANCE WITH THE
 ABOVE CODE.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  