2019-07-05 13:00:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. MARK THE FASTENING OPTIONS ON THE PRODUCT APPROVAL
 AS THEY DO NOT ALL MEET THE REQUIRED DESIGN PRESSURES,
 FBC B 1609.
  
 2. FBC B 1609, REVISE THE DESIGN PRESSURE/OPENING SIZE
 CHART; ZONE 5 IS SPECIFIED BUT IT APPEARS THAT ZONE 4
 PRESSURES WERE USED. ALSO IT STATES THAT THE ROOF
 HEIGHT IS 200', BUT 220' WAS CIRCLED ON THE
 ENGINEERING; DESIGN PRESSURE REQUIREMENTS ARE NOT
 CLEAR.
  
  