Plan Review Notes For Permit 19061193 |
Permit Number |
19061193 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-05 13:00:14 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. MARK THE FASTENING OPTIONS ON THE PRODUCT APPROVAL | | AS THEY DO NOT ALL MEET THE REQUIRED DESIGN PRESSURES, | | FBC B 1609. | | | | 2. FBC B 1609, REVISE THE DESIGN PRESSURE/OPENING SIZE | | CHART; ZONE 5 IS SPECIFIED BUT IT APPEARS THAT ZONE 4 | | PRESSURES WERE USED. ALSO IT STATES THAT THE ROOF | | HEIGHT IS 200', BUT 220' WAS CIRCLED ON THE | | ENGINEERING; DESIGN PRESSURE REQUIREMENTS ARE NOT | | CLEAR. | | | | |
|