Plan Review Notes
Plan Review Notes For Permit 19061180
Permit Number 19061180
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-26 16:10:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) COVER SHEET - THERE ARE NO INDICATIONS OF COMPLIANCE
 WITH ANY FIRE CODE
  
 THE PROPOSED PROJECT SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 6TH ED., AND ALL APPLICABLE ASSOCIATED
 CODES.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
  
 2) COVER SHEET AND A 2 - THERE ARE NO INDICATIONS OF
 FIRE SPRINKLER WORK.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND CEILINGS
 REQUIRES A REVIEW OF FIRE SPRINKLER PROTECTION.
  
 ANY FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
 3) COVER SHEET AND A 2 - THERE ARE NO INDICATIONS OF
 FIRE ALARM WORK. IT IS UNCLEAR IS ANY DEVICES WILL BE
 AFFECTED AR NEW ONES NEEDED.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND CEILINGS
 REQUIRES A REVIEW OF FIRE ALARM SYSTEM DEVICES.
  
 ANY FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  