2019-06-25 08:15:37RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF NOA 15-1201.09 SUBMITTED: SELECTED
 ASSEMBLY ON PAGE 41 OF 49 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED
 BY LIMITATION #7 ON LAST PAGE OF NOA. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: TAKE INTO CONSIDERATION THAT BUILDING IS LOCATED
 IN EXPOSURE D.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  