2019-07-05 08:38:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE THE INSTALLATION SCHEDULE TO STATE WHICH
 SHUTTER MOUNTING CONNECTION TYPE IS PROPOSED. C1, C4,
 C6, C8 ARE CIRCLED IN THE DETAILS, C8 REQUIRES 8"
 ANCHOR SPACING, BUT 9" IS PROPOSED FOR ALL OPENINGS.
  
 2. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  