Plan Review Notes For Permit 19061134 |
Permit Number |
19061134 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-07-05 08:38:36 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE THE INSTALLATION SCHEDULE TO STATE WHICH | | SHUTTER MOUNTING CONNECTION TYPE IS PROPOSED. C1, C4, | | C6, C8 ARE CIRCLED IN THE DETAILS, C8 REQUIRES 8" | | ANCHOR SPACING, BUT 9" IS PROPOSED FOR ALL OPENINGS. | | | | 2. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | |
|