Plan Review Notes
Plan Review Notes For Permit 19061116
Permit Number 19061116
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-28 11:04:57 
 1) SUBMIT TWO SETS OF A FLOOR PLAN SHOWING THE SCOPE OF
 WORK AND LOCATION OF THE SHOWER WITH SHOWER PAN
 DETAILS. FBC 107.2.1
  
 2) THE PLUMBING WORK TO BE DONE MUST BE DONE BY A
 LICENSED PLUMBING CONTRACTOR PER FL. STATUTE 489.
 SUBMIT A PERMIT APPLICATION FROM A CURRENTLY LICENSED
 PLUMBING CONTRACTOR. A CGC CANNOT INSTALL THE SHOWER
 PAN OR ANY PLUMBING ITEMS. WPB AMEND. TO FBC SEC.
 105.1.
  
 3) INDICATE ON THE REQUESTED PLANS IF A NEW SHOWER
 VALVE WILL BE INSTALLED. THE VALVE SHALL BE
 THERMOSTATIC OR PRESSURE-BALANCED.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 4) MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALL AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN 2017 FBC TABLE
 2509.2. INDICATE TYPE OF MATERIAL ON REQUESTED PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW