Plan Review Notes
Plan Review Notes For Permit 19061082
Permit Number 19061082
Review Stop G
Sequence Number 1
Notes
Date Text
2019-06-25 09:20:25GAS 1ST REVIEW**DENIED** GAS COMMENTS ON MASTER #
 19020826 WERE NEVER ANSWER AND REVIEW WAS COMPLETED
 WITH OUT A GAS REVIEW**
  
 1) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR THE
 TANKLESS WATER HEATER/ INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FGC SEC.305.1, FBC-RES. SEC.G2408.1. GAS
 APPLIANCES SHALL BE LISTED AND LABELED.
  
 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  