Plan Review Notes For Permit 19060970 |
Permit Number |
19060970 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-06-26 15:39:30 | 06/26/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. 1. THE TDH THAT WAS GIVEN OF 25 DOES NOT MATCH ON | | YOUR PUMP CURVE TO 100 GPM, PLEASE CONFIRM THE MAXIMUM | | SYSTEM FLOW FROM THE TDH CALCULATIONS. WPB AMENDMENTS | | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR | | THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO | | FBC SEC. 107.2.1. | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|