2019-10-02 15:24:26 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB |
| FBC 107.2.1, 107.3.5; FS 471, 481 (NOT PROVIDED.) |
| 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.) |
| 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| (LOAD CALCULATION PROVIDED IS NOT CORRECT. THERE SHOULD |
| BE A MINIMUM OF TWO SMALL APPLIANCE CIRCUITS AND ONE |
| LAUNDRY CIRCUIT INCLUDED IN THE CALCULATION AT 1500 VA |
| EACH. ADDITIONALLY, PALM BEACH COUNTY PROPERTY |
| APPRAISER STATES THAT THERE IS 2,448 SQUARE FEET UNDER |
| AIR, NOT THE 2,100 USED IN THE CALCULATION. PROVIDE |
| CORRECTIONS.) |
| 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT |
| PROVIDED.) |
| 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| 107.2.1 (NOT PROVIDED.) |
| |
| NEW COMMENTS: |
| |
| 7. CONTRACT PROVIDED STAES THAT THERE IS AN ELECTRICAL |
| UPGRADE INCLUDED WITH THIS PROJECT. DUE TO THE UPGRADE, |
| PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE |
| E3606.3 |
| 8. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND |
| PANELS. NEC 110.3, 110.9; FBC RE E3606.3 |
| 9. SPEC SHEET SHOWS TWO 50 AMP CIRCUITS TO TANKLESS |
| WATER HEATER ON 8/2 AWG. 8/2 ROMEX IS NOT RATED FOR 50 |
| AMPS. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| 334.80; FBC RE E3705.4.4; WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| |
| |